ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />
3.4.5 Auxiliary Relay Outputs<br />
EN54<br />
!<br />
From Relay<br />
circuits1 and 2<br />
on Base PCB<br />
EN54-2 8.8<br />
Fault Output:<br />
Relay 1 is configured<br />
for failsafe operation<br />
as standard.<br />
• The ZX1Se, ZX2Se and ZX5Se <strong>Fire</strong> Alarm Control <strong>Panels</strong> have<br />
two unsupervised relay outputs, with volt-free (dry contact),<br />
changeover contacts. The ZX10Se has four of these relays.<br />
• The contacts are rated at 30V AC/DC, 1 Amp.<br />
• Relay 1 is normally held in an energized state. It will de-energize<br />
under fault conditions.<br />
• Terminate the Auxiliary Relay circuit wiring at the Filter PCB installed at the left-hand side of the<br />
inside of the top cover of the back box. Refer to the figure below for wiring connection details to<br />
the Filter PCB.<br />
RL1<br />
To Filter PCB<br />
(Factory wired)<br />
RL2<br />
This edge is nearest front of panel<br />
Terminate external cables for<br />
Relay circuits 1 and 2 here<br />
+24V 0V A- A+ B- B+<br />
PL_LOOP2<br />
Figure 17 – Relay Output Terminal Connection Points – ZX1Se / ZX2Se<br />
N/O N/C COM N/O N/C COM A- A+ B- B+ C- C+ D- D+<br />
0V 24V<br />
TB10<br />
TB7 TB8 TB9 TB6<br />
_____ _____<br />
#1 #2<br />
RELAY CIRCUITS<br />
Figure 18 – Relay Output Terminal Connection Points – ZX5Se<br />
DO NOT connect non-power limited wiring to the relay contacts.<br />
<strong>Installation</strong> <strong>Manual</strong> Document No. 996-174-000-1, Revision: 01 Page 19