ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />

• It is recommended that Short Circuit Isolators be installed. Install the isolators at strategic points<br />

in the loop (i.e. zonal boundaries) to prevent an external short circuit from removing more than<br />

32 addressable points from the system.<br />

Note: The loop driver modules have built-in isolators so it is not required to place isolator modules<br />

on the outputs of the FACP.<br />

• Refer to the following diagram for information.<br />

FACP Connections<br />

Data / Power (+) OUT<br />

Data / Power (-) OUT<br />

Data / Power (+) RETURN<br />

Data / Power (-) RETURN<br />

Figure 11 – Loop Wiring with Isolators– Preferred Alternative<br />

DO NOT loop wiring under any terminals.<br />

EN54-2 requires that an isolator must be sited between each zone. You may use more than<br />

this, however, you must ensure that the loop wiring is broken at each isolation point.<br />

3.4.3.2 EMC Compliance<br />

For EMC Compliance, fit the<br />

Ferrite Absorbers supplied<br />

with the loop driver board<br />

around the SLC Loop cables.<br />

Cables should be screened<br />

and should be terminated in<br />

appropriate glands to meet<br />

local wiring codes and to<br />

preserve the integrity of the<br />

screen connection. The<br />

cable screen is to be<br />

clamped inside the cable<br />

gland, which must be fitted<br />

to ensure a 360° bond is<br />

formed with the metal of the<br />

back box. Alternatively,<br />

terminate the cable screens<br />

(drain wires) at the nearest<br />

earth stud provided on the<br />

inner top surface of the back<br />

box.<br />

The figure opposite shows<br />

the arrangement for a typical<br />

installation.<br />

Connect Earth drain<br />

wire of cables to nearest<br />

earth stud on inner, top<br />

wall of back box<br />

- keep length<br />

as short as possible<br />

ISOLATORS<br />

+ - E + -<br />

Absorber<br />

Large<br />

Affix cable tie<br />

around wires<br />

below ferrite<br />

Figure 12 – SLC Loop – EMC Absorber <strong>Installation</strong><br />