MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />
3.4.2.3 ZX5Se Arrangement<br />
• Included in the packing is a battery<br />
cable kit. Use the cable included in<br />
this kit to connect the negative<br />
terminal of battery No.1 to the<br />
positive terminal of battery No.2.<br />
• Connect the red wire from the Power<br />
Supply to the positive terminal of<br />
battery No.1.<br />
• Connect the black wire from the<br />
Power Supply to the negative<br />
terminal of battery No.2.<br />
• The standby batteries should be<br />
located in the enclosure as shown in<br />
the diagrams opposite. The chassis<br />
provides fixing points to allow a strap<br />
to be fitted.<br />
• For battery sizes greater then 12Ah, it<br />
may be necessary to cut off the<br />
spade terminals connected to the<br />
battery cables. These should be<br />
replaced by connector fixings<br />
appropriate to the installed batteries.<br />
Page 12 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong><br />
FS1 T 3.15A H 250V<br />
N L<br />
12Ah 12Ah<br />
Battery stop<br />
17Ah 17Ah<br />
Battery stop<br />
• When 24Ah batteries are used it will<br />
necessary to cut the cable ties that<br />
secure the wiring from the PSU below<br />
the Base PCB. Carefully re-route the<br />
wiring around the batteries after they<br />
have been installed. 24Ah 24Ah<br />
Battery stop<br />
Figure 8 – ZX5Se Battery <strong>Installation</strong><br />
• NOTE: When fitting 17Ah or 24Ah batteries there is insufficient space for fitting the internal printer<br />
module. In such cases the batteries should be fitted in a separate battery box (797-078) installed<br />
adjacent to the ZX Series FACP.<br />
3.4.2.4 General Battery Connection<br />
Black<br />
Wire<br />
- +<br />
Charger<br />
Output<br />
Link Wire<br />
- + - +<br />
2 1<br />
Red<br />
Wire