ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />

3.4.2 Battery <strong>Installation</strong><br />

3.4.2.1 General Introduction<br />

• Refer to the Standby Battery Calculations (Section 4) for the size of the batteries required for a<br />

particular installation.<br />

• Refer to Section 5.2.3 for a list of recommended batteries.<br />

Connect mains supply first then connect the batteries.<br />

Do not make the final battery connections until the installation is complete.<br />

Battery Lead Connections are not power limited.<br />

Before installation.<br />

New Batteries require ‘top charging’ prior to being put into service. For further<br />

information and for a list of recommended batteries, refer to Section 5.2.3.<br />

A thermistor on a flying lead may be provided. In this case, affix the thermistor to the side<br />

of one of the batteries using a commercially-available, silicon sealant.<br />

3.4.2.2 ZX1Se / ZX2Se Arrangement<br />

• Included in the packing is a battery cable kit. Use the cable included in this kit to connect the<br />

negative terminal of battery No.1 to the positive terminal of battery No.2.<br />

• Connect the red wire from terminal (7) of the Power Supply to the positive terminal of battery No.1.<br />

• Connect the black wire from terminal (8) of the Power Supply to the negative terminal of battery No.2.<br />

• Battery sizes up to 12Ah can be used and should be located in the enclosure as shown in the<br />

diagram below.<br />

• When fitting batteries ensure that the wiring between the outputs on the lower edge of the Base<br />

PCB and the Filter PCB is routed clear of the batteries as shown below.<br />

AUX<br />

SOUNDER<br />

O/P<br />

OUTPUTS<br />

POWER<br />

+24V 0V A- A+ B- B+ LIMITED<br />

7Ah<br />

or<br />

12Ah<br />

BATT<br />

MON<br />

AC<br />

MON<br />

EARTH<br />

EARTH<br />

+25V<br />

<strong>Installation</strong> <strong>Manual</strong> Document No. 996-174-000-1, Revision: 01 Page 11<br />

RELAY 1<br />

COM N/C N/O COM N/C N/O<br />

RELAY 1<br />

7Ah<br />

or<br />

12Ah<br />

RELAY 2<br />

Battery stops<br />

Figure 7 – ZX1Se / ZX2Se Battery <strong>Installation</strong><br />

RELAY 2<br />

FS1 FS2 FS3<br />

Fuse 250V A/S<br />

(FS1) 3.15A<br />

Fuse 250V A/S<br />

(FS2) 1.6A<br />

Fuse 250V A/S<br />

(FS3) 5.0A