ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />
3.4.2 Battery <strong>Installation</strong><br />
3.4.2.1 General Introduction<br />
• Refer to the Standby Battery Calculations (Section 4) for the size of the batteries required for a<br />
particular installation.<br />
• Refer to Section 5.2.3 for a list of recommended batteries.<br />
Connect mains supply first then connect the batteries.<br />
Do not make the final battery connections until the installation is complete.<br />
Battery Lead Connections are not power limited.<br />
Before installation.<br />
New Batteries require ‘top charging’ prior to being put into service. For further<br />
information and for a list of recommended batteries, refer to Section 5.2.3.<br />
A thermistor on a flying lead may be provided. In this case, affix the thermistor to the side<br />
of one of the batteries using a commercially-available, silicon sealant.<br />
3.4.2.2 ZX1Se / ZX2Se Arrangement<br />
• Included in the packing is a battery cable kit. Use the cable included in this kit to connect the<br />
negative terminal of battery No.1 to the positive terminal of battery No.2.<br />
• Connect the red wire from terminal (7) of the Power Supply to the positive terminal of battery No.1.<br />
• Connect the black wire from terminal (8) of the Power Supply to the negative terminal of battery No.2.<br />
• Battery sizes up to 12Ah can be used and should be located in the enclosure as shown in the<br />
diagram below.<br />
• When fitting batteries ensure that the wiring between the outputs on the lower edge of the Base<br />
PCB and the Filter PCB is routed clear of the batteries as shown below.<br />
AUX<br />
SOUNDER<br />
O/P<br />
OUTPUTS<br />
POWER<br />
+24V 0V A- A+ B- B+ LIMITED<br />
7Ah<br />
or<br />
12Ah<br />
BATT<br />
MON<br />
AC<br />
MON<br />
EARTH<br />
EARTH<br />
+25V<br />
<strong>Installation</strong> <strong>Manual</strong> Document No. 996-174-000-1, Revision: 01 Page 11<br />
RELAY 1<br />
COM N/C N/O COM N/C N/O<br />
RELAY 1<br />
7Ah<br />
or<br />
12Ah<br />
RELAY 2<br />
Battery stops<br />
Figure 7 – ZX1Se / ZX2Se Battery <strong>Installation</strong><br />
RELAY 2<br />
FS1 FS2 FS3<br />
Fuse 250V A/S<br />
(FS1) 3.15A<br />
Fuse 250V A/S<br />
(FS2) 1.6A<br />
Fuse 250V A/S<br />
(FS3) 5.0A