Display shows Description<br />

Version<br />

Configuration<br />

Language<br />

Change codeword<br />

Show and Set the Analogue outputs.<br />

AO1: Heating battery, Electric or hot-water. Show the output signal, 0-<br />

10V. Set the status to: Auto, Manual or Off. In Manual status it is<br />

possible to set the output signal within a range from 0 to10V.<br />

AO2 is shown only when the cooling function is activated.<br />

AO2: Cooling battery, cold-water. Show the output signal, 0-10V. Set the<br />

status to: Auto, Off or Manual. In Manual status it is possible to set the<br />

output signal within a range from 0 to10V.<br />

Show and Set the digital outputs, output 24V AC.<br />

DO1: Fan speed reduced. Activating the reduced fan speed relay. Show<br />

the status.<br />

DO2: Fan speed normal. Activating the normal fan speed relay. Show<br />

the status.<br />

DO3: Fresh air damper. Activating the fresh air damper. Show the<br />

status. Set the status to: Auto, On or Off.<br />

DO4: Alarm output. Summary alarm. Show the status. Set the status to:<br />

Auto, On or Off.<br />

Show the program version.<br />

Set the menu language.<br />

Note: A short cut to the menu language is by pressing the OK button at<br />

the same time as the main voltage is switched on.<br />

Set a new code for Service level.<br />