Industriële brandbeveiliging & Cases<br />

Deel 1<br />

Algemeen<br />

Stakeholders<br />

Historische ongevallen<br />

Proces brandrisicoanalyse<br />

Tools & techniques<br />

Cases<br />

Agenda<br />

21/05/2012<br />

1


Opslagloodsen<br />

Chemische installat<strong>ie</strong>s<br />

Ol<strong>ie</strong> & gas industr<strong>ie</strong><br />

Tankterminals<br />

Elektriciteitscentrales<br />

…<br />

Personenveiligheid<br />

Mil<strong>ie</strong>u<br />

Toepassingsgeb<strong>ie</strong>d<br />

Waarom industriële brandveiligheid?<br />

Bescherming van investering<br />

Bedrijfszekerheid<br />

Bedrijfsreputat<strong>ie</strong><br />

Wetgeving<br />

Verzekering<br />

21/05/2012<br />

2


Waarom risicoanalyse risicoanalyse ?<br />

Om te verzekeren dat potentiële incidenten geëvalueerd zijn<br />

naar type, yp , grootte g en gevolgen. g g<br />

Om brandveiligheidsmaatregelen te bepalen.<br />

Om specif<strong>ie</strong>ke vereisten voor specif<strong>ie</strong>ke risico’s te belichten.<br />

Om vereisten naar intervent<strong>ie</strong> eenheden te bepalen.<br />

Als formele basis om pre‐incident plannen te ontwikkelen.<br />

Guidelines<br />

• Industry<br />

• Codes & standards<br />

• Corporate p<br />

Requirements<br />

• Insurance<br />

• Legislation<br />

• Contractual<br />

• Fire brigade<br />

Stakeholders & Role FPE<br />

Tools &<br />

Methods<br />

•(Q)RA<br />

•PBFE<br />

Fire<br />

Sc<strong>ie</strong>nces<br />

•Fire dynamics<br />

•System<br />

techno.<br />

Fire Safety<br />

Strategy<br />

Organization<br />

• Goals<br />

• Tasks<br />

• People<br />

• Materials<br />

Infrastructure<br />

• Manufacturers<br />

• Contractors<br />

Customer<br />

21/05/2012<br />

3


Seveso II Direct<strong>ie</strong>ve<br />

ARAB / Vlarem<br />

Bijlage 6: Industr<strong>ie</strong>gebouwen<br />

Lokale regelgeving<br />

• Tankenparken richtlijn (Antwerpen)<br />

Wettelijk kader ‐ België<br />

Proact<strong>ie</strong>, prevent<strong>ie</strong>, preparat<strong>ie</strong>, repress<strong>ie</strong> en nazorg<br />

• Voor repress<strong>ie</strong> oa o.a.<br />

o Stationaire & mob<strong>ie</strong>le middelen, mensen<br />

o Containment<br />

o RWA‐installat<strong>ie</strong><br />

o Schuimconcentraat<br />

o Watervoorz<strong>ie</strong>ning<br />

Adv<strong>ie</strong>s brandweer<br />

o Aantal en type kleine blusmiddelen<br />

o Weerstand tegen bezwijken dragende construct<strong>ie</strong> opdat binnen<br />

aanval mogelijk is<br />

21/05/2012<br />

4


Shell (DEP’s)<br />

Total<br />

DOW Chemical<br />

BASF<br />

Bedrijfsrichtlijnen<br />

Industriële richtlijnen<br />

API (US)<br />

• API 2001 ‐ Fire Protection in Refinery<br />

• API 2021 0 ‐ Fighting Fires in and around Flammable and Combustible Liquid iquid Atmospheric<br />

Storage Tank<br />

• API 2030 ‐ Guidelines for Application of Water Spray Systems for Fire Protection in the<br />

Petroleum Industry<br />

• API 2218 ‐ Fireproofing practices in Petroleum and Petrochemical Processing Plants<br />

IP (UK)<br />

• IP Part 3 ‐ Refinery Safety Code<br />

• IP Part 9 ‐ Liquef<strong>ie</strong>d Petroleum Gas, Vol.1, Large Bulk Pressure storage and Refrigerated<br />

LPG<br />

• IP Part 19 ‐ Fire Precautions at Petroleum Refiner<strong>ie</strong>s and Bulk Storage Installations<br />

NFPA (US)<br />

• NFPA 30 ‐ Flammable and Combustible Liquids Code<br />

• NFPA 58 ‐ Liquef<strong>ie</strong>d Petroleum Gas<br />

• NFPA 68 ‐ Guide for Venting of Deflagrations<br />

• NFPA 69 ‐ Explosion Prevention Systems<br />

• NFPA 15 ‐ Water Spray Fixed Systems for Fire Protection<br />

21/05/2012<br />

5


FM<br />

AIG<br />

Munich RE<br />

AXA<br />

Fortis, ING<br />

Thema Gebouwen Industr<strong>ie</strong><br />

Eisen verzekeraars<br />

Building vs. Industrial<br />

Focus life safety property/business continuity<br />

Techn<strong>ie</strong>ken code compliance risico analyse<br />

Risico’s P(brand) = beperkt/<br />

C(brand) = aanz<strong>ie</strong>nlijk<br />

Awareness gemiddeld tot laag hoog<br />

Brandveiligheid structureel + detect<strong>ie</strong> /<br />

alarmering<br />

Budget<br />

eerder beperkt<br />

Impact FPE meer rigide omgeving<br />

Kennis FPE bouwkundig,human<br />

behaviour, etc..<br />

P (brand) = gemiddeld,<br />

C(brand) = (gemiddeld)<br />

intrins<strong>ie</strong>ke veiligheid, snelle detect<strong>ie</strong> +<br />

automatische blussing en on-site<br />

intervent<strong>ie</strong>team.<br />

afhankelijk van toegevoegde waarde<br />

meer flexibiliteit<br />

scheikunde, wiskunde, operationeel,<br />

etc…<br />

21/05/2012<br />

6


Flixborough, UK (1974)<br />

Cyclohexaanoxydat<strong>ie</strong><br />

Slecht ontwerp van reactorvervanging<br />

Flixborough<br />

Historische ongevallen<br />

Leiding begaf het<br />

→ vrijgave van 30 tot 100 ton cyclohexaan<br />

28 doden, 36 gewonden, plant volledig vern<strong>ie</strong>ld<br />

Max. overdruk<br />

→ in wolk: 5‐10 bar<br />

→ buitenzijde wolk: 0.7 bar<br />

21/05/2012<br />

7


Historische ongevallen<br />

PIPER ALPHA oil platform ‐ 1988<br />

Product<strong>ie</strong> platform in Noordzee (gas/ol<strong>ie</strong>)<br />

Initiële explos<strong>ie</strong> door:<br />

‐ Werken zonder juiste vergunning<br />

‐ Flens was n<strong>ie</strong>t lekdicht<br />

‐ Start pomp<br />

‐ Lek 45kg propaan en ontstekingsbron<br />

→ Procedure/communicat<strong>ie</strong> oorzaak<br />

Ol<strong>ie</strong>‐ en gasbranden<br />

167 doden, platform volledig vern<strong>ie</strong>ld<br />

Grootste verzekerde verl<strong>ie</strong>s ooit (2 800 Mill €)<br />

Proces Brandrisicoanalyse<br />

Start<br />

Kwalitat<strong>ie</strong>ve<br />

analyse<br />

Kwantitat<strong>ie</strong>ve<br />

analyse<br />

Criteria<br />

bereikt?<br />

JA<br />

Rapportage<br />

Presentat<strong>ie</strong><br />

Einde<br />

NEE<br />

21/05/2012<br />

8


Van gevaar tot incident<br />

Pijpleiding met<br />

vloeistof<br />

Klein/middelgroot/groot<br />

lek<br />

Plas<br />

in de tunnel<br />

Geen ontsteking Ontsteking<br />

in de tunnel<br />

Vloeistof in<br />

catch basin<br />

A<br />

Pool/trench fire<br />

in de tunnel<br />

B<br />

Literatuur<br />

Klein<br />

lek<br />

Gaswolk<br />

onder LEL<br />

Geen ontsteking Ontsteking<br />

in de tunnel<br />

Dispers<strong>ie</strong><br />

C<br />

Torch fire<br />

aan leiding<br />

In In‐house house exper<strong>ie</strong>nce<br />

NFPA<br />

Handboek kanscijfers<br />

D<br />

Lek in een pijpleiding<br />

Scenario Identificat<strong>ie</strong><br />

Pijpleiding met<br />

Gas<br />

Middelgroot<br />

lek<br />

Gaswolk<br />

tussen<br />

explos<strong>ie</strong>grenzen<br />

Geen ontsteking Ontsteking<br />

in de tunnel<br />

Dispers<strong>ie</strong><br />

E<br />

Explos<strong>ie</strong>:<br />

Deflagrat<strong>ie</strong><br />

F<br />

Explos<strong>ie</strong>:<br />

Detonat<strong>ie</strong><br />

G<br />

Groot<br />

lek<br />

Gaswolk<br />

boven UEL<br />

Geen ontsteking Ontsteking aan<br />

tunnelpoort<br />

Dispers<strong>ie</strong><br />

H<br />

Torch fire<br />

aan tunnelpoort<br />

Frequent<strong>ie</strong> ‐ lek<br />

Tabel 1: Faalfrequent<strong>ie</strong>s geclassificeerd op oorzaken en breukgrootte. Bron: EGIG.<br />

Faaloorzaken Faalfrequent<strong>ie</strong>s Percentage van Percentage van verschillende<br />

1<br />

[km j]<br />

totale faalkans<br />

( )<br />

grootte van de breuk [%]<br />

-1<br />

(-) klein middelgroot groot<br />

Externe invloeden 3.0 x 10 -4 Construct<strong>ie</strong>defecten 1.1 x 10<br />

51 % 25 56 19<br />

-4 Corros<strong>ie</strong> 8.1 x 10<br />

19 % 69 25 6<br />

-5 Grondbeweging 3.6 x 10<br />

14 % 97 3


Klein/middelgroot/groot<br />

lek<br />

P(r) = 1<br />

Geen ontsteking<br />

P(r) = 0.98<br />

Vloeistof in<br />

catch basin<br />

P(A) = 1.2 x 10-3<br />

Pijpleiding met<br />

vloeistof<br />

P(r) = 4/10<br />

Plas<br />

in de tunnel<br />

+ productdamp<br />

Ontsteking<br />

in de tunnel<br />

P(r) = 0.02<br />

Pool/trench fire/<br />

dampexplos<strong>ie</strong><br />

in de tunnel<br />

P(B) = 2.4 x 10-5<br />

Tank Fires<br />

Geen ontsteking<br />

P(r) = 0.98<br />

Dispers<strong>ie</strong><br />

P(C) = 1.2 x 10-3<br />

Klein<br />

lek<br />

P(r) = 0.71<br />

Gaswolk<br />

onder LEL<br />

Ontsteking<br />

in de tunnel<br />

P(r) = 0.02<br />

Torch fire<br />

aan leiding<br />

P(D) = 2.5 x 10-5<br />

Lek in een pijpleiding<br />

in de tunnel<br />

P(r) = 2.95 x 10-4 x 10<br />

Geen ontsteking<br />

P(r) = 0.98<br />

Dispers<strong>ie</strong><br />

P(E) = 3.8 x 10-4<br />

Frequent<strong>ie</strong> ‐ Event tree<br />

Gas jet fires<br />

Pijpleiding met<br />

gas<br />

P(r) = 6/10<br />

Middelgroot<br />

lek<br />

P(r) = 0.22<br />

Gaswolk<br />

tussen<br />

explos<strong>ie</strong>grenzen<br />

Pool fires Vapour Cloud<br />

Explosions<br />

Explos<strong>ie</strong>:<br />

Deflagrat<strong>ie</strong><br />

P(r) = 0.95<br />

P(F) = 0.7 x 10-5<br />

Ontsteking<br />

in de tunnel<br />

P(r) = 0.02<br />

Explos<strong>ie</strong>:<br />

Detonat<strong>ie</strong><br />

P(r) = 0.05<br />

P(G) = 3.9 x 10-7<br />

Geen ontsteking<br />

P(r) = 0.5<br />

Dispers<strong>ie</strong><br />

P(H) = 0.6 x 10-4<br />

Groot<br />

lek<br />

P(r) = 0.07<br />

Gaswolk<br />

boven UEL<br />

Ontsteking aan<br />

tunnelpoort<br />

P(r) = 0.5<br />

Torch fire<br />

aan tunnelpoort<br />

P(I) = 0.6 x 10-4<br />

Fire Scenarios<br />

BLEVE<br />

21/05/2012<br />

10


Modellering effecten<br />

Modellering effecten ‐ dispers<strong>ie</strong><br />

21/05/2012<br />

11


Modellering effecten –gas gas jet<br />

Modellering effecten ‐ UVCE<br />

Verbranding → expans<strong>ie</strong><br />

Lucht –gas mengsel vooruitgestuwd door<br />

vlammenfront<br />

Obstakels → turbulent<strong>ie</strong> → efficiëntere verbranding<br />

→ drukopbouw p<br />

Effecten afhankelijk van terrein!<br />

21/05/2012<br />

12


Modellering effecten ‐ UVCE<br />

Empirisch (vb. TNT, Multi‐energy, CAM)<br />

Fenomologisch (vb. SCOPE)<br />

CFD (vb. FLACS, Exsim)<br />

Voorbeeld: multi multi‐energy energy<br />

21/05/2012<br />

13


Drukgolf + vuurbal<br />

Drukgolf bepalende factor<br />

Stralingslim<strong>ie</strong>ten<br />

• Personenveiligheid<br />

Modellering effecten ‐ BLEVE<br />

Interpretat<strong>ie</strong> effecten<br />

o 1.5 kW.m ‐2 : lim<strong>ie</strong>t voor lange onbeschermde blootstelling<br />

o 3 kW.m ‐2 : korte onbeschermde blootstelling<br />

o 10 kW.m ‐2 : korte blootstelling in beschermende kledij<br />

• Installat<strong>ie</strong>s<br />

o 10 kW.m ‐2 : faling sturingen<br />

o 37 5 kW m ‐2 o 37,5 kW.m : faling tanks en ander equipment<br />

2 : faling tanks en ander equipment<br />

Dispers<strong>ie</strong><br />

• LEL: onderste explos<strong>ie</strong>grens<br />

• UEL: bovenste explos<strong>ie</strong>grens<br />

21/05/2012<br />

14


Overdruk<br />

Interpretat<strong>ie</strong> effecten<br />

• 10 mbar: glasbreuk<br />

• 20 mbar: typische veiligheidsafstand, geen significante<br />

schade onder deze grenswaarde<br />

• 70 mbar: huizen onbewoonbaar, ge<strong>deel</strong>telijke instorting<br />

• 170 mbar: 50% van wanden in baksteen vern<strong>ie</strong>tigd<br />

• 200 mbar: stalen construct<strong>ie</strong>s afgerukt van fundering<br />

• 250 mbar: opslagtanks gescheurd<br />

• 350 mbar: houten palen afgeknapt<br />

• 480 mbar: geladen wagons omvergeblazen<br />

Site: ondergrondse gasopslag<br />

Doel Doel: evaluat<strong>ie</strong> van brandbestrijdingsmiddelen<br />

• Evaluat<strong>ie</strong> huidige middelen<br />

• Adv<strong>ie</strong>s nodige maatregelen<br />

• Veiligheidsconcept<br />

Method<strong>ie</strong>k: scenarioanalyse<br />

• SSelect<strong>ie</strong> l ti representat<strong>ie</strong>ve tti scenario’s i ’<br />

• Modellering effecten<br />

• Bepaling bestrijdingsmiddelen<br />

Case study<br />

21/05/2012<br />

15


Gasvrijzetting<br />

• Dispers<strong>ie</strong><br />

• Gasdeb<strong>ie</strong>t na inblokking<br />

• Straling gasjet<br />

Vrijzetting vloeistof<br />

• Straling plasbrand<br />

BLEVE opslagtanks<br />

• Overdruk<br />

UVCE compressorruimte<br />

• Overdruk<br />

Case: gasopslag<br />

Scenario’s<br />

21/05/2012<br />

16


Gasvrijzetting<br />

Effect op site<br />

21/05/2012<br />

17


Densiteit in funct<strong>ie</strong> van stralingsimpact<br />

Doel Doel: waterfilm houdt temperatuur equipment<br />

beperkt<br />

Koeling<br />

Blussystemen<br />

21/05/2012<br />

18


Case: depot<br />

Groot depot voor transportvoertuigen met hoge<br />

waarde<br />

Vraagstelling eigenaar:<br />

• Risico verl<strong>ie</strong>s van eigendom?<br />

• Risico bedrijfszekerheid?<br />

(Case dateert van voor bijlage 6)<br />

Projectbeschrijving<br />

21/05/2012<br />

19


Onderhoudshall<br />

• Geklassificeerd als ‘industr<strong>ie</strong>el industr<strong>ie</strong>el gebouw’ gebouw<br />

• Vloeroppervlakte: 5 000 m2<br />

• 10 voertuigen<br />

• Machines, werktuigen, atel<strong>ie</strong>rs<br />

Depot<br />

• Geklassificeerd als ‘opslaggebouw’<br />

opslaggebouw<br />

• Vloeroppervlakte: +10 000 m2<br />

• 100 voertuigen<br />

Automatische & manuele detect<strong>ie</strong><br />

Ontruimingsinstallat<strong>ie</strong><br />

Opdeling depot<br />

Beveiligingsmaatregelen<br />

Brandslanghaspels en handbrandblussers<br />

Noodsignalisat<strong>ie</strong><br />

Eerste intervent<strong>ie</strong>team<br />

21/05/2012<br />

20


Doel van het project<br />

Adv<strong>ie</strong>s rond de installat<strong>ie</strong> van een sprinklersysteem op<br />

basis van een kosten – baten analyse<br />

• Analyse en inschatting van brandrisico’s in depot en<br />

onderhoudshall<br />

• Inschatting van gevolgschade<br />

• Inschatting installat<strong>ie</strong>‐ en operationele kost van<br />

sprinklersysteem<br />

• Inschatting van de gevolgen van de plaatsing van een<br />

sprinklersysteem<br />

Decision<br />

Class<br />

Decision<br />

Context<br />

Class A •Nothing new or unusual<br />

•Well understood risk<br />

•Established Risk<br />

Class B •Life cycle implications<br />

•Some risk trade‐offs<br />

•Some uncertainty or deviation from standard<br />

or best practice<br />

•Economic implications<br />

Fire Risk Assessment<br />

Approach<br />

•Codes & Standards<br />

•Good Practice<br />

•Engineering Judgment<br />

•Fire Protection System ‐ Layer of<br />

Protection Analysis (FPS‐LOPA) which<br />

provides order of magnitude risk<br />

estimates based on specific cause‐<br />

consequence scenarios.<br />

Method<strong>ie</strong>k<br />

Remarks<br />

Eas<strong>ie</strong>st to apply, generally<br />

uses qualitative<br />

risk analysis<br />

Simplif<strong>ie</strong>d quantitative<br />

Risk‐informed evaluation<br />

methods are gaining<br />

popularity in Industry.<br />

Class C •Very Very novel /challenging<br />

•Quantitative Quantitative Risk Assessment (QRA)<br />

Most demanding on<br />

•Significant risk trade‐offs<br />

which provides additional detail resources and skill sets,<br />

•Large uncertaint<strong>ie</strong>s<br />

regarding event contributing factors, but delivers most detailed<br />

•Strong stake holder v<strong>ie</strong>ws or perceptions risk reduction options, and<br />

understanding and best<br />

cost/benefit analysis.<br />

decision basis if major<br />

expenditures are involved.<br />

21/05/2012<br />

21


COMMUNITY EMERGENCY RESPONSE<br />

PLANT EMERGENCY RESPONSE<br />

MITIGATION SYSTEMS<br />

Passive Protection Systems<br />

Active Engineering Controls<br />

Active Suppression Systems<br />

Procedural Controls<br />

PREVENTION MEASURES<br />

Safety Instrumented Systems (SIS)<br />

Ignition Controls<br />

Procedural Controls<br />

PROCESS & FACILITY DESIGN<br />

Inherently Safe Design Features<br />

Basic Process Controls<br />

Projectaanpak: LOD<br />

Case 2:Project Approach ‐ LOPA<br />

21/05/2012<br />

22


Definit<strong>ie</strong> brandscenario’s<br />

Projectaanpak ‐ LOPA<br />

Vastleggen frequent<strong>ie</strong> brand (gebeurtenissen/jaar)<br />

Quantificeer prestat<strong>ie</strong> van IFPL’s<br />

Evaluat<strong>ie</strong> gevolgschade<br />

Inschatting van risico van scenario<br />

Risico‐evaluat<strong>ie</strong><br />

Risico‐reduct<strong>ie</strong><br />

Wat:<br />

• Branden d<strong>ie</strong> significante schade veroorzaken aan:<br />

Definit<strong>ie</strong> scenario’s<br />

o Voertuigen<br />

o Eigendom<br />

Bronnen:<br />

• Literatuur, interv<strong>ie</strong>ws, bezoek ter plaatse, engineering judgement<br />

o Depot<br />

⁻ Ol<strong>ie</strong>lek<br />

⁻ Afval<br />

⁻ Kortsluiting<br />

⁻ Brandstichting<br />

o Onderhoudshall<br />

⁻ Heet werk<br />

⁻ Defecte apparatuur<br />

⁻ Ol<strong>ie</strong>lek<br />

⁻ Brandstichting<br />

21/05/2012<br />

23


Ontsteking<br />

Brandontwikkeling<br />

Automatische detect<strong>ie</strong> & alarmering<br />

Manuele detect<strong>ie</strong> & alarmering<br />

Eerste intervent<strong>ie</strong><br />

Automatische blussing<br />

Tussenkomst brandweer<br />

Sources (S) Layer of Fire Protection Systems in Pathway (P) Targets (T)<br />

Definit<strong>ie</strong> scenario’s<br />

Opbouw event tree<br />

[ A ] [ B ] [ C ] [ D ] [ E ] [ F ] [G] [H] [I] [J] [K] [L]<br />

Initiating Fire Auto detection Manual Intervention Sprinkler Fire Branch Branch Property Damage Risk/year<br />

Fire Event Growth and alarm Detection Operation System Service Line Line Damage Exposure Mo<strong>net</strong>ary<br />

and Alarm Exposure Total value in €<br />

Likelihood Successful Successful Successful Successful Successful Sucessful I.D. Likelihood Level % in €<br />

1 0,00E+00<br />

E1<br />

2 0,00E+00<br />

C1 F1<br />

3 0,00E+00<br />

E2 G1<br />

F2 4 0,00E+00<br />

G2<br />

B1<br />

5 0,00E+00<br />

E3<br />

0,2 6 0,00E+00<br />

D1 F3<br />

7 0,00E+00<br />

E4 G3<br />

YES C2 F4 8 0,00E+00 0<br />

Fires / Year NO G4<br />

9 0,00E+00<br />

F5<br />

10 0,00E+00<br />

D2 G5<br />

F6 11 0,00E+00 0<br />

G6<br />

1 12 0,00E+00<br />

B2<br />

CHECK 0,00E+00 Total annualized risk/year<br />

0<br />

Industriële Brandveiligheid – Cursus RUG<br />

21/05/2012<br />

24


Ontstekingsfrequent<strong>ie</strong><br />

Belangrijke parameter: bepaalt grootte‐orde van<br />

gebeurtenissen<br />

Data voor depots zijn schaars: slechts 2 gekende<br />

incidenten<br />

Alternat<strong>ie</strong>ve methodes te gebruiken, vb. BS<br />

F = a ⋅ A<br />

• F i is ontstekingsfrequent<strong>ie</strong> (per jaar)<br />

• A c is vloeroppervlakte in het gebouw in m 2<br />

• a en b zijn constanten, gerelateerd aan de gebouwclassificat<strong>ie</strong><br />

i<br />

b<br />

c<br />

Onstekingsfrequent<strong>ie</strong><br />

21/05/2012<br />

25


Depot<br />

Ontstekingsfrequent<strong>ie</strong><br />

• Onsteking 00.073/jaar 073/jaar = 7 ontstekingen over 100 jaar<br />

Onderhoudshall<br />

• Ontsteking 0.14/year = 1 ontsteking over 10 jaar<br />

Kans op gebeurtenissen<br />

• Statistische data en literatuur<br />

• BS en SFPE vormen goede bronnen<br />

Wijzigingen ind<strong>ie</strong>n nodig op basis van<br />

• Interv<strong>ie</strong>ws<br />

• Bezoek ter plaatse<br />

• Engineering judgement<br />

Kans op gebeurtenissen<br />

21/05/2012<br />

26


Kans op gebeurtenissen<br />

[ A ] [ B ] [ C ] [ D ] [ E ] [ F ] [G] [H] [I] [K] [L]<br />

Initiating Fire Auto detection Manual Intervention Sprinkler Fire Branch Branch Damage Risk/year<br />

Fire Event Growth and alarm Detection Operation System Service Line Line Exposure Mo<strong>net</strong>ary<br />

and Alarm Total value in €<br />

Likelihood Successful Successful Successful Successful Successful Sucessful I.D. Likelihood in € 2,67E+08<br />

0,5 1 1,43E-02<br />

E1<br />

0,85 0 2 0,00E+00<br />

C1 F1<br />

0,5 1 3 1,43E-02<br />

E2 1 G1<br />

F2 0 4 0,00E+00<br />

0,46 G2<br />

B1<br />

0,5 5 5,04E-04<br />

E3<br />

0,2 0 6 0,00E+00<br />

D1 F3<br />

0,5 0,95 7 4,79E-04<br />

0,15 E4 1 G3<br />

7,30E-02 YES C2 F4 0,05 8 2,52E-05<br />

Fires es / Year ea NOO G4 G<br />

0 9 0,00E+00<br />

F5<br />

0,8 0,05 10 2,01E-04<br />

D2 1 G5<br />

F6 0,95 11 3,83E-03<br />

G6<br />

0,54 12 3,94E-02<br />

B2<br />

CHECK 7,30E-02 0<br />

Event<br />

ID<br />

Event<br />

Success<br />

-<br />

Failure<br />

Kans op gebeurtenissen<br />

Probability [1] Basis-Remarks- References<br />

A Ignition frequency -<br />

0,0731 per<br />

year<br />

[1] See previous section<br />

S 0,46 Fire growth probabilit<strong>ie</strong>s are dependent on the<br />

occupancy type of the building and the<br />

B Fire growth<br />

activit<strong>ie</strong>s. These values are modif<strong>ie</strong>d to reflect<br />

F 0,54 the actual activit<strong>ie</strong>s and depot [1], [2], [3], [5],<br />

[15].<br />

C<br />

D<br />

E<br />

F<br />

Auto detection<br />

alarm<br />

Manual<br />

detection/alarm<br />

Man Manual al<br />

suppression<br />

No<br />

sprinkler/sprinkler<br />

G Fire service<br />

S 0,85 Detection system will be designed for 90%<br />

performance. However, the building is open<br />

and the detection system can be prone to<br />

F 0,15 external conditions such as weather and<br />

reliability can be decreased [4], [1].<br />

S 0,2 The only occupants in the site are 2 security<br />

guards. The probability of the fire being<br />

F 0,8<br />

detected in its early stages is small.<br />

Engineering judgement [4].<br />

S 0,5/0,5 Based on the fact that it is a slow developing<br />

fire with ith a power po er of 200kW, 200kW the inter intervention ention<br />

F 0,5/0,5<br />

team will have a 50% success/failure to<br />

extinguish the fire. Engineering judgement [4].<br />

S 0/0,85 Sprinkler system will be designed for property<br />

protection. System reliability value from<br />

literature is given as 90% [1], [3], [4], [11]. The<br />

system however will be designed as a dry<br />

F 1/0,15 system due to open structure and prone to<br />

weather, i.e. freezing. Success is modif<strong>ie</strong>d to<br />

0.85.<br />

S 1,0/0,95/0,05 If manual and automatic detection fails, the fire<br />

will eventually be detected by a third party, i.e.<br />

neighbours. If this occurs the fire will already be<br />

F 0,0/0,05/0,95<br />

of considerable size. Engineering judgement<br />

Industriële Brandveiligheid – Cursus RUG<br />

[16].<br />

[1] Success and failure<br />

values separated by a<br />

slash “/” refer to<br />

different events, i.e. E1,<br />

E2, E3 etc… See event<br />

trees<br />

21/05/2012<br />

27


Schade aan eigendom<br />

• Verl<strong>ie</strong>s depot = 35 mill €<br />

• Verl<strong>ie</strong>s inhoud = 180 mill €<br />

• Bedrijfszekerheid = 50 mill €<br />

PPotent<strong>ie</strong>el i lverl<strong>ie</strong>s li = 265 mill ill €<br />

Gevolgschade<br />

Geen sprinklerbeveiliging<br />

Sources (S) Layer of Fire Protection Systems in Pathway (P) Targets (T)<br />

[ A ] [ B ] [ C ] [ D ] [ E ] [ F ] [G] [H] [I] [J] [K] [L]<br />

Initiating Fire Auto detection Manual Intervention Sprinkler Fire Branch Branch Property Damage Risk/year<br />

Fire Event Growth and alarm Detection Operation System Service Line Line Damage Exposure Mo<strong>net</strong>ary<br />

and Alarm Exposure Total value in €<br />

Likelihood Successful Successful Successful Successful Successful Sucessful I.D. Likelihood Level % in € 2,67E+08<br />

0,5 1 1,43E-02<br />

E1<br />

0,85 0 2 0,00E+00<br />

C1 F1<br />

0,5 1 3 1,43E-02<br />

E2 1 G1<br />

F2 0 4 0,00E+00<br />

0,46 G2<br />

B1<br />

0,5 5 5,04E-04<br />

E3<br />

0,2 0 6 0,00E+00<br />

D1 F3<br />

0,5 0,95 7 4,79E-04<br />

0,15 ,<br />

E4 1 G3<br />

7,30E-02 YES C2 F4 0,05 8 2,52E-05<br />

Fires / Year NO G4<br />

0 9 0,00E+00<br />

F5<br />

0,8 0,05 10 2,01E-04<br />

D2 1 G5<br />

F6 0,95 11 3,83E-03 100,000% 266.540.000 1.020.347<br />

G6<br />

0,54 12 3,94E-02 0,000% 0<br />

B2<br />

CHECK 7,30E-02 Total annualized risk/year<br />

1.020.347<br />

21/05/2012<br />

28


Sprinklerbeveiliging<br />

Sources (S) Layer of Fire Protection Systems in Pathway (P) Targets (T)<br />

[ A ] [ B ] [ C ] [ D ] [ E ] [ F ] [G] [H] [I] [J] [K] [L]<br />

Initiating Fire Auto detection Manual Intervention Sprinkler Fire Branch Branch Property Damage Risk/year<br />

Fire Event Growth and alarm Detection Operation System Service Line Line Damage Exposure Mo<strong>net</strong>ary<br />

and Alarm Exposure Total value in €<br />

Likelihood Successful Successful Successful Successful Successful Sucessful I.D. Likelihood Level in % in € 2,67E+08<br />

0,5 1 1,43E-02 1,43E 02 0<br />

E1<br />

0,85 0,85 2 1,21E-02 0<br />

C1 F1<br />

0,5 1 3 2,14E-03 0<br />

E2 0,15 G1<br />

F2 0 4 0,00E+00 0<br />

0,46 G2<br />

A1<br />

0,5 5 5,04E-04 0<br />

E3<br />

0,2 0,85 6 4,28E-04 0<br />

D1 F3<br />

0,5 0,95 7 7,18E-05 0<br />

0,15 E4 0,15 G3<br />

7,30E-02 YES C2 F4 0,05 8 3,78E-06 0<br />

Fires / Year NO G4<br />

0,85 9 3,43E-03 0<br />

F5<br />

0,8 0,05 10 3,02E-05 0<br />

D2 0,15 G5<br />

F6 0,95 11 5,74E-04 100,000% 266.540.000 153.052<br />

G6<br />

0,54 12 3,94E-02 0,000% 0<br />

B2<br />

21/05/2012<br />

CHECK 7,30E-02 Total annualized risk/year 153.052<br />

Financial risk per year<br />

1.200.000<br />

1.000.000<br />

800.000<br />

600.000<br />

400.000<br />

200.000<br />

150.000<br />

1.000.000<br />

Verwacht verl<strong>ie</strong>s<br />

150.000<br />

60 60.000 000<br />

6.000 10.000<br />

0<br />

Depot Service Hall; Day Service Hall; Night<br />

Sprinklered 150.000 6.000 10.000<br />

Non Sprinklered 1.000.000 60.000 150.000<br />

21/05/2012<br />

29


Financial<br />

risk per year<br />

Kost van sprinkler systeem<br />

• Installat<strong>ie</strong> = 900K€<br />

• Operationeel = 5k€<br />

Gespreid op 30 jaar = 35 k€/jaar<br />

35.000.000<br />

30.000.000<br />

25.000.000<br />

20.000.000<br />

15.000.000<br />

10.000.000<br />

Kosten –baten baten analyse<br />

Case 2 : Project Analysis ‐ CBA<br />

30.000.000<br />

5.000.000<br />

55.000.000 000 000 44.500.000 500 000<br />

1.800.000<br />

800.000<br />

1.000.000<br />

0<br />

Depot Service Hall; Day Service Hall; Night<br />

Sprinklered 5.000.000 800.000 1.000.000<br />

Non Sprinklered 30.000.000 1.800.000 4.500.000<br />

21/05/2012<br />

30


Besluit<br />

Frequent<strong>ie</strong> van scenario met grote verl<strong>ie</strong>zen is zeer<br />

laag<br />

Gevolgschade is zeer hoog<br />

Totaal risico is aanz<strong>ie</strong>nlijk<br />

Kosten – baten analyse voor sprinklersysteem wijst uit<br />

dat investering gerechtvaardigd is<br />

Mogelijk bijkomende beveiling nodig om jaarlijks<br />

risico verder te verlagen<br />

Besluit LOPA<br />

LOPA geeft inzicht over volledig risicoprof<strong>ie</strong>l en<br />

afhankelijkheden<br />

LOPA laat toe om kosten‐baten analyse over<br />

grootteorde te maken<br />

Akkoord nodig voor frequent<strong>ie</strong> en waarschijnlijkheden<br />

tussen verschillende partijen<br />

21/05/2012<br />

31


Werkt als volgt: volgt<br />

Dow Brand & Explos<strong>ie</strong> Index<br />

• Straf voor onveilige situat<strong>ie</strong><br />

• Bonus voor beheersing en mitigat<strong>ie</strong><br />

Uitkomst is een getal ‐ hoe hoger, hoe meer risico<br />

Enkel voor brandbare materialen<br />

N<strong>ie</strong>t efficiënt voor procedures<br />

Beoordeling Brandrisico (F&EI) (F&EI)<br />

11 februari 2009<br />

21/05/2012<br />

32


Materiaalfactor<br />

• Gebaseerd op N Nf en Nr<br />

(NFPA 704 diamant)<br />

Type proces<br />

• Endotherm<br />

• Exotherm<br />

• Binnen of buiten<br />

Toegang tot de site<br />

Drainage<br />

4<br />

3<br />

W<br />

3<br />

11 februari 2009<br />

F&EI<br />

Algemene Proces Proces‐Gevaren Gevaren<br />

11 februari 2009<br />

21/05/2012<br />

33


Toxisch materiaal<br />

Vacuüm druk<br />

Werking boven vlampunt<br />

Stofexplos<strong>ie</strong>s<br />

Werkingsdruk<br />

Lage temperatuur<br />

Hoeveelheid materiaal in proces p<br />

Corros<strong>ie</strong><br />

Ovens in de omgeving<br />

…<br />

General Process Hazards Factor F1<br />

Special Process Hazards factor F2<br />

Unit hazard factor F3<br />

F3 = F1 * F2<br />

F&EI= MF * F3<br />

Specif<strong>ie</strong>ke Proces Proces‐Gevaren Gevaren<br />

11 februari 2009<br />

Bepaal F&EI<br />

11 februari 2009<br />

21/05/2012<br />

34


F&EI bepaalt schadecirkel<br />

Financiële Schade<br />

Vervangingswaarde => > Base Maximum Probable<br />

Property Damage (BMPPD)<br />

Vermenigvuldigen met beschermingsfactoren<br />

• Procescontrole<br />

• Materiaalisolat<strong>ie</strong><br />

• BBrandbeveiliging db ili i<br />

Leidt tot de Actual MPPD<br />

H<strong>ie</strong>rmee kunnen dagen buiten d<strong>ie</strong>nst ingeschat<br />

worden<br />

11 februari 2009<br />

Dagen buiten d<strong>ie</strong>nst<br />

11 februari 2009<br />

21/05/2012<br />

35


Literatuur<br />

SFPE (Soc<strong>ie</strong>ty of Fire Protection Engineers) Handbook of Fire Protection Engineering, 3rd<br />

edition; 2002<br />

Robert G. G Zalosh – Industrial Fire Protection Engineering –Wiley Wiley, 2003<br />

Thomas F. Bary – Risk‐Informed, Performance‐based Industrial Fire Protection, An Alternative<br />

to Prescriptive Codes, Tenessee Valley Publishing, 2002<br />

Guidelines for Fire Protection in Chemical, Petrochemical, and Hydrocarbon Processing<br />

Facilit<strong>ie</strong>s. Center for Chemical Process Safety, Center for Chemical Process Safety/AIChE, 2003<br />

REFERENCE GUIDE FOR HAZARD ANALYSIS IN PV FACILITIES, Brookhaven National Laboratory<br />

Upton, New York 11973‐5000, 2003. (free download from www.nrel.org)<br />

Health & Safety Executive, UK. (lots of info & free downloads from HSE website)<br />

NFPA (National Fire Protection Association, USA)<br />

API (American Petroleum Institute)<br />

IP (Institute of Petroleum, UK) Model Code of Safe Practice<br />

Shell’s DEP (Design and Engineering Practice)<br />

21/05/2012<br />

36