2009-2017 Long Range Transmission Study<br />

The long range transmission study is a steady-state assessment <strong>of</strong> the adequacy <strong>of</strong> the FRCC’s<br />

bulk and 69 kV transmission system for 2009-2017. The NERC Transmission Planning Standards are<br />

used to gauge the adequacy <strong>of</strong> the transmission system. These transmission planning standards state<br />

that the transmission system must remain stable within the applicable thermal and voltage rating limits<br />

without cascading outages, under normal system conditions, as well as during single and multiple<br />

contingency events. The FRCC’s Long Range Transmission Reliability Study covers both near-term<br />

and long-term portions <strong>of</strong> the planning horizon. The near-term part examines years two through five<br />

(2009-2012) and analyzes in detail specific remedies identified for all thermal and/or voltage<br />

screening criteria exceptions. The long-term section examines years six through ten (2013-2017) to<br />

determine if any trends are developing that would require attention.<br />

The Long Range Transmission Reliability Study for transmission facilities, 69kV and greater,<br />

within the FRCC Region concluded that potential thermal and voltage screening criteria violations can<br />

be resolved by operator intervention meeting the NERC Transmission Planning Standards. The<br />

resolutions were thoroughly reviewed by the transmission owners and found to be adequate in order to<br />

maintain acceptable system performance under all conditions and events. The FRCC found no major<br />

projects requiring long lead times.<br />

Florida-Southern Interface Transfer Capability Study<br />

Currently, Peninsular Florida imports 1,702 MW <strong>of</strong> firm capacity into the FRCC region from<br />

the Southern Control Area within the SERC region (Southern). The remaining transferrable capacity,<br />

nearly 2,000 MW, is available through non-firm energy sales. Firm capacity exports to Southern do<br />

not occur at this time, nor are they forecasted to occur during the planning horizon. The FRCC and<br />

Southern annually perform an interregional transmission study to confirm the maximum import and<br />

export capability between the two regions and to make sure that the transmission plans <strong>of</strong> both regions<br />

jointly meet the NERC reliability standards. Based on studies performed by the FRCC and Southern,<br />

there do not appear to be any reliability constraints at the Florida-Southern interface at this time<br />

concerning the current use <strong>of</strong> interface capacity. The 2007 study confirmed the total transfer<br />

capabilities between the FRCC and Southern, which are contained in Table 13 below.<br />

Table 13. Florida-Southern Interface Transfer Capability<br />

Transfer<br />

Transfer Capability (MW)<br />

Summer Winter<br />

Southern to Florida (import) 3600 3700<br />

Florida to Southern (export) 1000 2100<br />