files still contained a variety of cases unrelated to high fronted guttering including leaking downpipes, incomplete work and aesthetic problems. On this basis, the Committee found only five specific problems relating to the functional aspects of high fronted guttering and a further five where inadequately designed downpipes or similar created adverse conditions likely to directly affect the performance of high fronted guttering. From this data it can be said that there has been a low incidence of complaints registered with NSW Fair Trading concerning high fronted guttering. For instance, the database information could potentially cover complaints as much as 10 years old given that work carries a seven year statutory warranty after completion (under Section 18B and 18E of the Home Building Act 1989), and therefore any complaints recorded in 2007 could theoretically span as far back as 2000. Over this period and up to 2010 there has been considerable new housing construction (Australian Bureau of Statistics 87310) and in addition to this, there is consensus from those presenting to the Committee that the gutter replacement market is much larger than the new housing market. As such, it is apparent that the above stated number of complaints represents a very small proportion of overall guttering work over this period. Case Specific Data Despite the above over-arching data, the Committee sought out and reviewed information on certain specific cases dealt with by NSW Fair Trading. Though such cases are isolated and as such do not constitute sufficient grounds for substantiating a “systemic problem”, they do provide insight into problematic areas that could be improved regarding the use of high fronted guttering. Of note, a number of these cases fall into the category of gutter replacement. Here, it is common for traditional low-front guttering (which automatically provides good overflow characteristics) to be replaced by high fronted guttering (where targeted overflow management is more critical). It is apparent from these cases, that there is a greater need to consider not only overflow measures but the design of cross sectional gutter area and downpipe sizes as well (or even additional downpipes). Where high fronted guttering replaces existing guttering and no consideration is made of the downpipes and storm water drainage capacity required to get surface water away in conjunction with replacing the guttering, there will always be a high risk of water ingress into the building. In such instances, slots alone may not be adequate in preventing overflow that enters the building. This supports the need for a more measurable approach to overflow devices where high fronted guttering is involved in replacing low front gutters. Operation Flow- A NSW Fair Trading Study of the Building Code of Compliance on Display Homes NSW Fair Trading Inspectors through Operation Flow appraised a range of display homes in mid- 2010 throughout NSW (35 in total), concerning their compliance with BCA performance requirements and AS3500 requirements. The main focus was on the number of downpipes and for evidence of overflow measures. Visual inspections of eaves linings and, where it was possible, internal walls and ceilings were conducted for signs of damage through water ingress into the building as a result of overflow. NSW Fair Trading wrote to builders seeking advice on how they conformed to AS3500 requirements (Note: albeit that this is only one means of meeting BCA performance requirements). Not all had responded at the time of completing this report. Inspectors, through their calculations, advised of widespread under-design of downpipes to meet the AS3500 20 year ARI requirements in the homes appraised. For a small number of homes they also noted signs of water damage to eaves linings, but the causes were not precisely quantified. 17

Inspectors advised that all homes except for one were not compliant with AS3500 in regard to the adequate provision of downpipes, but then made the additional observations that the majority were compliant with BCA performance requirements i.e. as a result of lack of evidence of water damage from gutter overflow. The Committee believes these were perhaps lenient interpretations of the BCA and ideally should have checked to determine the maximum rainfall intensity that the homes had been exposed to, in order to draw conclusions about how well the homes were meeting BCA performance requirements. In addition, independent auditing by an expert adviser to the Committee of the calculations made by Inspectors was undertaken on eight dwellings. Though the exact calculations made by the expert varied from those of the inspectors, the expert still agreed with the conclusion that the houses studied did not comply with AS3500.3 or “Acceptable Construction Practice”. It revealed inconsistencies and inaccuracies in the calculations. The expert also said that it is hard to determine whether or not the dwellings comply with the basic performance measure of avoiding flows into a dwelling under the 100 year ARI – stating that gutters tend to overflow at low points thereby reducing the load on the downpipe system and that some gutters distort under full load and the distortion permits a discharge of water reducing the peak load. The audit report also found that AS3500.3 provides more rather than less downpipes and guttering than the BCA’s own “Acceptable Construction Practice” for the 20 year ARI. It would seem that the latter, in general, provides a more lenient basis for meeting BCA performance requirements. As a result of the above findings, there is a concern by the Committee of a lack of adherence and understanding in industry concerning the use of Deemed to Satisfy solutions and the calculation methods involved in specifying the gutter size and number of downpipes to suit the roof area for a given 20 year ARI. Though evidence here is limited, there is concern about a lack of downpipes to deal with the ARI. Whilst such problems effect the compliance of all guttering systems trying to meet Deemed to Satisfy compliance, it is clear that high fronted guttering are more sensitive to the effects of such problems due to the ramifications that a lack of downpipe drainage has on overflow entry into a building. Informal overflow mechanisms – mentioned previously - may to an unknown extent assist in mitigating the chances of such overflow. The Insurance Council of Australia(ICA) The ICA formally advised the Committee that there was no systemic problem their members were able to identify in relation to high fronted guttering. Industry Parties Individual manufacturers, the Housing Industry Association (HIA) and the Australian Steel Institute provided advice to the Committee that they still had (following on from meetings held in 2008) no evidence of a systemic problem concerning high fronted guttering in NSW, or elsewhere in Australia. The Committee was satisfied that a relatively small number of manufacturers dominated the guttering market – each made individual representations to the Committee. A number of them provided sales data to demonstrate that the vast majority of their sales involve high fronted guttering i.e. high fronted gutters represent between 65-86% of the overall eaves gutter market. Evidence was also presented by one manufacturer (by way of a historically significant advertising brochure) that high fronted guttering have been in the market place some 40 years, since 1970. The 18

Inspectors advised that all homes except for one were not compliant with AS3500 in regard to the<br />

adequate provision of downpipes, but then made the additional observations that the majority were<br />

compliant with BCA performance requirements i.e. as a result of lack of evidence of water damage<br />

from gutter overflow.<br />

The Committee believes these were perhaps lenient interpretations of the BCA and ideally should<br />

have checked to determine the maximum rainfall intensity that the homes had been exposed to, in<br />

order to draw conclusions about how well the homes were meeting BCA performance requirements.<br />

In addition, independent auditing by an expert adviser to the Committee of the calculations made by<br />

Inspectors was undertaken on eight dwellings. Though the exact calculations made by the expert<br />

varied from those of the inspectors, the expert still agreed with the conclusion that the houses<br />

studied did not comply with AS3500.3 or “Acceptable Construction Practice”. It revealed<br />

inconsistencies and inaccuracies in the calculations. The expert also said that it is hard to determine<br />

whether or not the dwellings comply with the basic performance measure of avoiding flows into a<br />

dwelling under the 100 year ARI – stating that gutters tend to overflow at low points thereby<br />

reducing the load on the downpipe system and that some gutters distort under full load and the<br />

distortion permits a discharge of water reducing the peak load. The audit <strong>report</strong> also found that<br />

AS3500.3 provides more rather than less downpipes and <strong>guttering</strong> than the BCA’s own “Acceptable<br />

Construction Practice” for the 20 year ARI. It would seem that the latter, in general, provides a more<br />

lenient basis for meeting BCA performance requirements.<br />

As a result of the above findings, there is a concern by the Committee of a lack of adherence and<br />

understanding in industry concerning the use of Deemed to Satisfy solutions and the calculation<br />

methods involved in specifying the gutter size and number of downpipes to suit the roof area for a<br />

given 20 year ARI. Though evidence here is limited, there is concern about a lack of downpipes to<br />

deal with the ARI. Whilst such problems effect the compliance of all <strong>guttering</strong> systems trying to<br />

meet Deemed to Satisfy compliance, it is clear that high <strong>front</strong>ed <strong>guttering</strong> are more sensitive to the<br />

effects of such problems due to the ramifications that a lack of downpipe drainage has on overflow<br />

entry into a building. Informal overflow mechanisms – mentioned previously - may to an unknown<br />

extent assist in mitigating the chances of such overflow.<br />

The Insurance Council of Australia(ICA)<br />

The ICA formally advised the Committee that there was no systemic problem their members were<br />

able to identify in relation to high <strong>front</strong>ed <strong>guttering</strong>.<br />

Industry Parties<br />

Individual manufacturers, the Housing Industry Association (HIA) and the Australian Steel Institute<br />

provided advice to the Committee that they still had (following on from meetings held in 2008) no<br />

evidence of a systemic problem concerning high <strong>front</strong>ed <strong>guttering</strong> in <strong>NSW</strong>, or elsewhere in Australia.<br />

The Committee was satisfied that a relatively small number of manufacturers dominated the<br />

<strong>guttering</strong> market – each made individual representations to the Committee. A number of them<br />

provided sales data to demonstrate that the vast majority of their sales involve high <strong>front</strong>ed<br />

<strong>guttering</strong> i.e. high <strong>front</strong>ed gutters represent between 65-86% of the overall eaves gutter market.<br />

Evidence was also presented by one manufacturer (by way of a historically significant advertising<br />

brochure) that high <strong>front</strong>ed <strong>guttering</strong> have been in the market place some 40 years, since 1970. The<br />