22.08.2013 Views

Impact of leading power factor loads on synchronous ... - Cummins Inc.

Impact of leading power factor loads on synchronous ... - Cummins Inc.

Impact of leading power factor loads on synchronous ... - Cummins Inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Power topic #6001 | Technical informati<strong>on</strong> from <strong>Cummins</strong> Power Generati<strong>on</strong><br />

<str<strong>on</strong>g>Impact</str<strong>on</strong>g> <str<strong>on</strong>g>of</str<strong>on</strong>g> <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g><br />

<str<strong>on</strong>g>factor</str<strong>on</strong>g> <str<strong>on</strong>g>loads</str<strong>on</strong>g> <strong>on</strong><br />

synchr<strong>on</strong>ous alternators<br />

> White paper


Power topic #6001 | Page 2<br />

The generator set AVR m<strong>on</strong>itors generator output voltage<br />

and c<strong>on</strong>trols alternator field strength to maintain<br />

c<strong>on</strong>stant output voltage. Relatively low AVR output is<br />

required to maintain generator voltage at no load. In the<br />

figure shown, the no load exciter field current required<br />

is less than half the full load level.<br />

Filter equipment is <str<strong>on</strong>g>of</str<strong>on</strong>g>ten sized for operati<strong>on</strong> at the<br />

expected maximum load <strong>on</strong> the UPS or motor load.<br />

At light <str<strong>on</strong>g>loads</str<strong>on</strong>g> there may be excess filter capacitance,<br />

causing a <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g>. Since rectifiers are<br />

comm<strong>on</strong>ly designed to ramp <strong>on</strong> from zero load to<br />

minimize load transients, <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g> <str<strong>on</strong>g>loads</str<strong>on</strong>g><br />

may be imposed <strong>on</strong> the system until inductive <str<strong>on</strong>g>loads</str<strong>on</strong>g> are<br />

added to the system or the load <str<strong>on</strong>g>factor</str<strong>on</strong>g> <str<strong>on</strong>g>of</str<strong>on</strong>g> the n<strong>on</strong>linear<br />

load increases.<br />

A utility supply simply absorbs the reactive <str<strong>on</strong>g>power</str<strong>on</strong>g><br />

output because it is extremely large relative to the<br />

filter system and it has many <str<strong>on</strong>g>loads</str<strong>on</strong>g> that can c<strong>on</strong>sume<br />

this energy. With a generator set, however, the rising<br />

voltage from the <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g> causes the<br />

voltage regulator to turn down and reduce alternator<br />

field strength. If the AVR turns all the way <str<strong>on</strong>g>of</str<strong>on</strong>g>f it looses<br />

c<strong>on</strong>trol <str<strong>on</strong>g>of</str<strong>on</strong>g> system voltage, which can result in sudden<br />

large increases in system voltage. The increase in<br />

voltage can result in damage to <str<strong>on</strong>g>loads</str<strong>on</strong>g>, or can cause<br />

the <str<strong>on</strong>g>loads</str<strong>on</strong>g> to fail to operate <strong>on</strong> the generator set.<br />

A UPS is designed to recognize high voltage as an<br />

abnormal and undesirable c<strong>on</strong>diti<strong>on</strong>, so it can immediately<br />

switch <str<strong>on</strong>g>of</str<strong>on</strong>g>f its rectifier. When it does that, the<br />

high voltage c<strong>on</strong>diti<strong>on</strong> is immediately relieved (because<br />

the filter is disc<strong>on</strong>nected from the generator set) and<br />

voltage returns to normal. To the observer, the generator<br />

will seem to be unable to pick up the system <str<strong>on</strong>g>loads</str<strong>on</strong>g>.<br />

Paralleling problems<br />

Generator sets that are using in isolated bus paralleling<br />

systems have particular issues with <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g><br />

<str<strong>on</strong>g>factor</str<strong>on</strong>g> <str<strong>on</strong>g>loads</str<strong>on</strong>g>.<br />

When <str<strong>on</strong>g>loads</str<strong>on</strong>g> are applied to a parallel generator bus, the<br />

total load <strong>on</strong> the system can be many times larger than<br />

the capacity <str<strong>on</strong>g>of</str<strong>on</strong>g> a single generator set. The generator<br />

sets close to the bus <strong>on</strong>e at a time, so that if high<br />

<str<strong>on</strong>g>loads</str<strong>on</strong>g> (either <str<strong>on</strong>g>leading</str<strong>on</strong>g> or lagging) are applied before<br />

genset capacity is available, the generator bus can fail.<br />

With <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g> <str<strong>on</strong>g>loads</str<strong>on</strong>g>, the failure mode will<br />

be due to either an over voltage c<strong>on</strong>diti<strong>on</strong> or reverse<br />

kVAR shutdown. due to either an overvoltage c<strong>on</strong>diti<strong>on</strong><br />

or due to reverse kVAR shutdown.<br />

www.cummins<str<strong>on</strong>g>power</str<strong>on</strong>g>


Per Unit kW<br />

Power topic #6001 | Page 3<br />

outside <str<strong>on</strong>g>of</str<strong>on</strong>g> normal range. Notice that as <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g><br />

drops, the machine must be de-rated to prevent<br />

overheating. On the left quadrant, you can see that<br />

near-normal output (yellow area) can be achieved with<br />

some <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g> load, in this case, down<br />

to about 0.97 <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g>, <str<strong>on</strong>g>leading</str<strong>on</strong>g>. At that point, the<br />

ability to absorb additi<strong>on</strong>al kVAR quickly drops to near<br />

zero (red area), indicating that the AVR is “turning <str<strong>on</strong>g>of</str<strong>on</strong>g>f”<br />

and any level <str<strong>on</strong>g>of</str<strong>on</strong>g> reverse kVAR greater than the level<br />

shown will cause the machine to lose c<strong>on</strong>trol <str<strong>on</strong>g>of</str<strong>on</strong>g> voltage.<br />

In other words, if the machine is rated for operati<strong>on</strong> at<br />

1000 kVA and 0.8 <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g> (600 kVAR rated), with<br />

a reverse kVAR level <str<strong>on</strong>g>of</str<strong>on</strong>g> 0.2 per unit (rated), you will<br />

exceed the machine’s capabilities. So, with more than<br />

120 kVAR reverse reactive <str<strong>on</strong>g>power</str<strong>on</strong>g> and <str<strong>on</strong>g>leading</str<strong>on</strong>g> <str<strong>on</strong>g>power</str<strong>on</strong>g><br />

<str<strong>on</strong>g>factor</str<strong>on</strong>g> lower than 0.97 (for most people a surprisingly<br />

low level) we have a problem.<br />

The ability <str<strong>on</strong>g>of</str<strong>on</strong>g> a generator set to absorb reactive<br />

<str<strong>on</strong>g>power</str<strong>on</strong>g> is defined by a reverse kVAR limit, not a<br />

specific <str<strong>on</strong>g>power</str<strong>on</strong>g> <str<strong>on</strong>g>factor</str<strong>on</strong>g>.<br />

ALTERNATOR CAPABILITY CURVE<br />

1.1<br />

1.0<br />

0.9<br />

0.8<br />

0.7<br />

0.6<br />

0.5<br />

0.4<br />

0.3<br />

0.2<br />

0.1<br />

0.0<br />

1.0<br />

www.cummins<str<strong>on</strong>g>power</str<strong>on</strong>g>


Power topic #6001 | Page 4<br />

About the author

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!