Electrical <strong>Troubleshooting</strong> Procedures <strong>LTC</strong> <strong>Repair</strong><br />
6.19 Checking Voltage at the Main Circuit Breaker<br />
See Graphic: wc_gr003786<br />
WARNING<br />
Electric shock hazard. Only qualified personnel should conduct this<br />
test. Do not perform this test if you or the machine are wet.<br />
Complete this test with the machine running.<br />
6.19.1 Remove the control panel front cover.<br />
6.19.2 Using the AC voltage setting on the multimeter, measure the voltage<br />
between the two incoming terminals (a) of the main circuit breaker.<br />
There should be 230V±10%.<br />
If 230V±10% was not measured, shut down the machine and<br />
check the continuity of the wiring back to the short terminal strip.<br />
<strong>Repair</strong> the wiring as necessary.<br />
If 230V±10% was measured, continue.<br />
6.19.3 Place the main circuit breaker in the ON position and measure the<br />
voltage between the two outgoing terminals of the main circuit breaker.<br />
If 230V±10% was not measured, shutdown the machine and<br />
replace the main circuit breaker.<br />
If 230V±10% was measured, the wiring and main circuit breaker<br />
are functioning properly.<br />