Electrical <strong>Troubleshooting</strong> Procedures <strong>LTC</strong> <strong>Repair</strong><br />

6.19 Checking Voltage at the Main Circuit Breaker<br />

See Graphic: wc_gr003786<br />

WARNING<br />

Electric shock hazard. Only qualified personnel should conduct this<br />

test. Do not perform this test if you or the machine are wet.<br />

Complete this test with the machine running.<br />

6.19.1 Remove the control panel front cover.<br />

6.19.2 Using the AC voltage setting on the multimeter, measure the voltage<br />

between the two incoming terminals (a) of the main circuit breaker.<br />

There should be 230V±10%.<br />

If 230V±10% was not measured, shut down the machine and<br />

check the continuity of the wiring back to the short terminal strip.<br />

<strong>Repair</strong> the wiring as necessary.<br />

If 230V±10% was measured, continue.<br />

6.19.3 Place the main circuit breaker in the ON position and measure the<br />

voltage between the two outgoing terminals of the main circuit breaker.<br />

If 230V±10% was not measured, shutdown the machine and<br />

replace the main circuit breaker.<br />

If 230V±10% was measured, the wiring and main circuit breaker<br />

are functioning properly.<br />

98