Electrical <strong>Troubleshooting</strong> Procedures <strong>LTC</strong> <strong>Repair</strong><br />

6.29 Checking Receptacle’s Circuit Breaker<br />

See Graphic: wc_gr003081<br />

WARNING<br />

Electric shock hazard. Only qualified personnel should conduct this<br />

test.<br />

Complete this test with the machine running.<br />

6.29.1 Using the AC voltage setting on the multimeter, measure the incoming<br />

voltage to the receptacle’s circuit breaker by measuring between the<br />

brown-yellow wire (a) and the wires (b) of the terminal strip. There<br />

should be 115V or 230V±10% depending on model.<br />

If the correct voltage is not measured, the receptacle’s circuit<br />

breaker is not receiving voltage. Check the condition of the wiring<br />

between the receptacle’s circuit breaker and the terminal strip.<br />

<strong>Repair</strong>/replace the wiring as needed.<br />

If the correct voltage is measured, continue.<br />

6.29.2 Make sure the receptacle’s circuit breaker is in the ON position.<br />

6.29.3 Using the AC voltage setting on the multimeter, measure the outgoing<br />

voltage from the receptacle’s circuit breaker by measuring between the<br />

outgoing wire (c) and the wires (b) of the terminal strip. There should<br />

be 115V or 230V±10% depending on model.<br />

If the correct voltage is not measured, the receptacle’s circuit<br />

breaker is not functioning. Confirm that receptacle’s circuit<br />

breaker is malfunctioning by checking its continuity. Replace the<br />

circuit breaker if needed.<br />

If the correct voltage is measured, continue troubleshooting by<br />

checking the earth-leakage circuit breaker.<br />

b<br />

1000<br />

F 200 V<br />

20<br />

2<br />

200m<br />

V- COM<br />

A<br />

1000<br />

F 200 V<br />

20<br />

2<br />

200m<br />

V- COM<br />

118<br />

A<br />

a<br />

c<br />

wc_gr003081