19.08.2013 Views

Catalog LV1 T 2009 Chapter 3 EN

Catalog LV1 T 2009 Chapter 3 EN

Catalog LV1 T 2009 Chapter 3 EN

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3<br />

3RT, 3TB, 3TF Contactors for Switching Motors<br />

3RT10 contactors, 3-pole, 3 ... 250 kW<br />

Contactors Size S00 S0 ... S12<br />

s and u ratings of the auxiliary contacts<br />

1) For more information about short-circuit values, e. g. for protection against<br />

short-circuit currents, see the UL guide (Order No.: A5E02118883 for<br />

German) or UL reports (http://www.siemens.com/lowvoltage/support) for<br />

the individual devices.<br />

3/54<br />

Siemens LV 1 T · <strong>2009</strong><br />

Screw terminals and<br />

Cage Clamp terminals<br />

Integrated or<br />

snap-on<br />

auxiliary switch block<br />

Screw terminals and<br />

Cage Clamp terminals<br />

1- and 4-pole<br />

snap-on<br />

auxiliary switch block<br />

Screw terminals and<br />

Cage Clamp terminals<br />

Laterally<br />

mountable<br />

auxiliary switch block<br />

Rated voltage V AC 600 600 600<br />

Switching capacity A 600, Q 600 A 600, Q 600 A 300, Q 300<br />

Uninterrupted current<br />

at 240 V AC A 10 10 10<br />

Contactors Type 3RT10 54 3RT10 55 3RT10 56 3RT10 64 3RT10 65 3RT10 66<br />

Size S6 S6 S6 S10 S10 S10<br />

s and u ratings<br />

Rated insulation voltage V AC 600 600<br />

Uninterrupted current, at 40 °C<br />

Maximum horsepower ratings<br />

(s and u approved values)<br />

Open and enclosed A 140 195 195 250 330 330<br />

Rated power for induction motors<br />

At 200 V hp 40 50 60 60 75 100<br />

at 60 Hz<br />

230 V hp 50 60 75 75 100 125<br />

460 V hp 100 125 150 150 200 250<br />

575 V hp 125 150 200 200 250 300<br />

Short-circuit protection1) At 600 V kA 10 10 10 10 18 18<br />

CLASS RK5/L fuse A 450 500 500 700 800 800<br />

Circuit breakers with overload<br />

protection acc. to UL 489<br />

A 350 450 500 500 700 800<br />

NEMA/EEMAC ratings<br />

NEMA/EEMAC size hp -- 4 -- -- -- 5<br />

Uninterrupted current - Open A -- 150 -- -- -- 300<br />

- Enclosed A -- 135 -- -- -- 270<br />

Rated power<br />

for induction motors<br />

with 60 Hz<br />

At 200 V hp -- 40 -- -- -- 75<br />

230 V hp -- 50 -- -- -- 100<br />

460 V hp -- 100 -- -- -- 200<br />

575 V hp -- 100 -- -- -- 200<br />

Overload relay Type 3RB20 56 3RB20 66<br />

Contactors Type 3RT10 75 3RT10 76<br />

Size S12 S12<br />

s and u ratings<br />

Rated insulation voltage V AC 600<br />

Uninterrupted current, at 40 °C<br />

Maximum horsepower ratings<br />

(s and u approved values)<br />

Open and enclosed A 400 540<br />

Rated power for induction motors<br />

At 200 V hp 125 150<br />

at 60 Hz<br />

230 V hp 150 200<br />

460 V hp 300 400<br />

575 V hp 400 500<br />

Short-circuit protection 1)<br />

At 600 V kA 18 30<br />

CLASS L fuse A 1000 1200<br />

Circuit breakers with overload protection<br />

acc. to UL 489<br />

A 900 900<br />

NEMA/EEMAC ratings<br />

NEMA/EEMAC size hp -- 6<br />

Uninterrupted current - Open A -- 600<br />

- Enclosed A -- 540<br />

Rated power for induction motors<br />

at 60 Hz<br />

© Siemens AG <strong>2009</strong><br />

Overload relay Type 3RB20 66<br />

At 200 V hp -- 150<br />

230 V hp -- 200<br />

460 V hp -- 400<br />

575 V hp -- 400