1) For more information about short-circuit values, e. g. for protection against<br />
short-circuit currents, see the UL guides (Order No.: A5E02118883 for<br />
German) or UL reports (http://www.siemens.com/lowvoltage/support) for<br />
the individual devices.<br />
© Siemens AG <strong>2009</strong><br />
3RT, 3TB, 3TF Contactors for Switching Motors<br />
3RT10 contactors, 3-pole, 3 ... 250 kW<br />
Contactors Type 3RT10 15 3RT10 16 3RT10 17 3RT10 23 3RT10 24 3RT10 25 3RT10 26<br />
Size S00 S00 S00 S0 S0 S0 S0<br />
s and u ratings<br />
Rated insulation voltage V AC 600 600<br />
Uninterrupted current, at 40 °C<br />
Maximum horsepower ratings<br />
(s and u approved values)<br />
Open and enclosed A 20 35<br />
Rated power for induction motors<br />
At 200 V hp 1.5 2 3 2 3 5 7.5<br />
at 60 Hz<br />
230 V hp 2 3 3 3 3 5 7.5<br />
460 V hp 3 5 7.5 5 7.5 10 15<br />
575 V hp 5 7.5 10 7.5 10 15 20<br />
Short-circuit protection 1)<br />
At 600 V kA 5 5 5 5 5 5 5<br />
(contactor or overload relay) CLASS RK5 fuse A 60 60 60 70 70 70 100<br />
Circuit breakers with overload<br />
protection acc. to UL 489<br />
A 50 50 50 70 70 70 100<br />
Combination motor controllers<br />
type E acc. to UL 508<br />
-At 480V Type-- -- -- 3RV10 2<br />
A -- -- -- 8 10 16 22<br />
kA -- -- -- 65 65 65 65<br />
-At 600V Type-- -- -- 3RV10 2<br />
A -- -- -- 8 10 12.5 12.5<br />
kA -- -- -- 25 25 25 25<br />
NEMA/EEMAC ratings<br />
NEMA/EEMAC size hp -- 0 -- 1<br />
Uninterrupted current - Open A -- 18 -- 27<br />
-Enclosed A -- 18 -- 27<br />
Rated power for induction motors<br />
At 200 V hp -- 3 -- 7.5<br />
at 60 Hz<br />
230 V hp -- 3 -- 7.5<br />
460 V hp -- 5 -- 10<br />
575 V hp -- 5 -- 10<br />
Overload relay Type 3RU11 16 3RU11 2<br />
Setting range A 0.11 ... 12 1.8 ... 25<br />
Contactors Type 3RT10 34 3RT10 35 3RT10 36 3RT10 44 3RT10 45 3RT10 46<br />
Size S2 S2 S2 S3 S3 S3<br />
s and u ratings<br />
Rated insulation voltage V AC 600 600<br />
Uninterrupted current, at 40 °C<br />
Maximum horsepower ratings<br />
(s and u approved values)<br />
Open and enclosed A 45 55 50 90 105 105<br />
Rated power for induction motors<br />
At 200 V hp 10 10 15 20 25 30<br />
at 60 Hz<br />
230 V hp 10 15 15 25 30 30<br />
460 V hp 25 30 40 50 60 75<br />
575 V hp 30 40 50 60 75 100<br />
Short-circuit protection1) At 600 V kA 5 5 5 10 10 10<br />
(contactor or overload relay) CLASS RK5 fuse A 125 150 200 250 300 350<br />
Circuit breakers with overload protection<br />
acc. to UL 489<br />
A 125 150 200 250 300 400<br />
Combination motor controllers<br />
type E acc. to UL 508<br />
-At 480V Type3RV10 3 3RV10 4<br />
A 32 40 50 63 75 100<br />
kA 65 65 65 65 65 65<br />
-At 600V Type3RV10 4 3RV10 4<br />
A 32 40 50 63 75 75<br />
kA 25 25 25 30 30 30<br />
NEMA/EEMAC ratings<br />
NEMA/EEMAC size hp -- 2 -- 3<br />
Uninterrupted current - Open A -- 45 -- 90<br />
-Enclosed A -- 45 -- 90<br />
Rated power<br />
At 200 V hp -- 10 -- 25<br />
for induction motors with 60 Hz<br />
230 V hp -- 15 -- 30<br />
460 V hp -- 25 -- 50<br />
575 V hp -- 25 -- 50<br />
Overload relay Type 3RU11 3 3RU11 4<br />
Setting range A 5.5 ... 50 18 ... 100<br />
Siemens LV 1 T · <strong>2009</strong><br />
3/53<br />