1) Depending on the electronic ballast used, higher lamp numbers are also<br />

possible.<br />

3RT, 3TB, 3TF Contactors for Switching Motors<br />

3RT10 contactors, 3-pole, 3 ... 250 kW<br />

Contactors Type 3RT10 44 3RT10 45 3RT10 46<br />

Main circuit<br />

AC capacity<br />

Size S3 S3 S3<br />

Utilization category AC-4 (for Ia = 6 x Ie) Rated operational current Ie Up to 400 V A 55 66 80<br />

Rated power for squirrel-cage motors<br />

with 50 Hz and 60 Hz<br />

The following applies to a contact endurance<br />

of about 200000 operating cycles:<br />

At 400 V kW 30 37 45<br />

- Rated operational currents Ie Up to 400 V<br />

690 V<br />

A<br />

A<br />

28<br />

28<br />

34<br />

34<br />

42<br />

42<br />

1000 V A 20 23 23<br />

- Rated power for squirrel-cage<br />

motors with 50 Hz and 60 Hz<br />

At 230 V kW 8.7 10.4 12<br />

400 V kW 15.1 17.9 22<br />

500 V kW 18.4 22.4 27<br />

690 V kW 25.4 30.9 38<br />

1000 V kW 22 30 30<br />

Utilization category AC-5a<br />

Switching gas discharge lamps, inductive ballast<br />

Per main current path at 230 V<br />

Uncorrected,<br />

rated power per lamp/rated operational current per lamp<br />

L 18 W/0.37 A Units 270 324<br />

L 36 W/0.43 A Units 232 279<br />

L 58 W/0.67 A Units 149 179<br />

L 80 W/0.79 A Units 126 151<br />

DUO switching (two-lamp)<br />

L 18 W/0.21 A Units 454 (r 2x454lamps) 545 (r 2x545lamps)<br />

L 36 W/0.42 A Units 238 (r 2x238lamps) 285 (r 2x285lamps)<br />

L 58 W/0.63 A Units 158 (r 2x158lamps) 190 (r 2x190lamps)<br />

L 80 W/0.87 A Units 114 (r 2x114lamps) 137 (r 2x137lamps)<br />

Switching gas discharge lamps with correction<br />

Per main current path at 230 V<br />

Shunt compensation with inductive ballast,<br />

rated power per lamp/capacitance/rated<br />

operational current per lamp<br />

© Siemens AG <strong>2009</strong><br />

L 18 W/4.5 μF/0.11 A Units 160 197 234<br />

L 36 W/4.5 μF/0.21 A Units 160 197 234<br />

L58 W/7 μF/0.32 A Units 103 127 150<br />

L80 W/7 μF/0.49 A Units 103 126 146<br />

With solid-state ballast1) single lamp<br />

L 18 W/6.8 μF/0.10 A Units 455 560 665<br />

L 36 W/6.8 μF/0.18 A Units 253 311 369<br />

L58 W/10 μF/0.29 A Units 156 193 229<br />

L80 W/10 μF/0.43 A Units 105 130 154<br />

With solid-state ballast 1) two-lamp<br />

L18 W/10 μF/0.18 A Units 253 (r 2x253lamps) 311 (r 2x311lamps) 369 (r 2x369lamps)<br />

L36 W/10 μF/0.35 A Units 130 (r 2x130lamps) 160 (r 2x160lamps) 190 (r 2x190lamps)<br />

L58 W/22 μF/0.52 A Units 88 (r 2x88lamps) 108 (r 2x108lamps) 128 (r 2x128lamps)<br />

L80 W/22 μF/0.86 A Units 52 (r 2x52lamps) 65 (r 2x65lamps) 77 (r 2x77lamps)<br />

Utilization category AC-5b<br />

Switching incandescent lamps<br />

Per main current path at 230/220 V kW 12.3 15.2 18.1<br />

Siemens LV 1 T · <strong>2009</strong><br />

3/35<br />

3