3RT, 3TB, 3TF Contactors for Switching Motors<br />
3RT10 contactors, 3-pole, 3 ... 250 kW<br />
Contactors Type 3RT10 23 3RT10 24 3RT10 25 3RT10 26<br />
Size S0 S0 S0 S0<br />
Conductor cross-sections (1 or 2 conductors connectable)<br />
Main conductors Screw terminals<br />
Conductor cross-section<br />
Solid mm² 2 x (1 ... 2.5) 1) ; 2 x (2.5 ... 6) 1) Finely stranded with end sleeve mm²<br />
acc. to IEC 60947; max. 1 x 10<br />
2 x (1 ... 2.5) 1) ; 2 x (2.5 ... 6) 1)<br />
AWG cables, solid AWG 2 x (16 ... 12)<br />
AWG cables,<br />
AWG 2 x (14 ... 10)<br />
solid or stranded<br />
AWG cables, stranded AWG 1 x 8<br />
Terminal screws M4 (Pozidriv size 2)<br />
- Tightening torque<br />
Auxiliary conductors<br />
Nm 2 ... 2.5 (18 ... 22 lb.in)<br />
Conductor cross-section<br />
Solid mm 2<br />
2 x (0.5 ... 1.5) 1) ; 2 x (0.75 ... 2.5) 1) acc. to IEC 60947;<br />
max. 2 x (0.75 ... 4)<br />
Finely stranded with end sleeve mm2 2 x (0.5 ... 1.5) 1) ; 2 x (0.75 ... 2.5) 1)<br />
solid or stranded AWG (2 x) AWG 2 x (20 ... 16) 1) ; 2 x (18 ... 14) 1) ; 1 x 12<br />
Terminal screws M3<br />
- Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)<br />
Auxiliary conductors Cage Clamp terminals<br />
Solid mm<br />
1)<br />
If two different conductor cross-sections are connected to one clamping<br />
point, both cross-sections must lie in the range specified. If identical crosssections<br />
are used, this restriction does not apply.<br />
2<br />
Finely stranded with end sleeve mm<br />
2 x (0.25 ... 2.5)<br />
2<br />
Finely stranded without end sleeve mm<br />
2 x (0.25 ... 1.5)<br />
2 2 x (0.25 ... 2.5)<br />
AWG cables,<br />
solid or stranded<br />
AWG 2 x (24 ... 14)<br />
Contactors Type 3RT10 34 3RT10 35 3RT10 36<br />
Size S2 S2 S2<br />
General data<br />
Permissible mounting position<br />
The contactors are designed for<br />
operation on a vertical mounting<br />
surface.<br />
3/28<br />
Siemens LV 1 T · <strong>2009</strong><br />
AC and DC operation<br />
Upright mounting position: AC and DC operation<br />
Mechanical endurance Basic units Operating<br />
cycles<br />
Special version required.<br />
10 million<br />
Basic unit with snap-on auxiliary<br />
switch block<br />
10 million<br />
Solid-state compatible auxiliary<br />
switch block<br />
5 million<br />
Electrical endurance<br />
1)<br />
Rated insulation voltage Ui (degree of pollution 3) V 690<br />
Rated impulse withstand voltage U imp kV 6<br />
Protective separation between the coil and the main contacts<br />
acc. to <strong>EN</strong> 60947-1, Appendix N<br />
© Siemens AG <strong>2009</strong><br />
V 400<br />
30° 30°<br />
For DC operation and 22.5 ° inclination towards the front,<br />
operating range 0.85 ... 1.1 x U s<br />
Mirror contacts<br />
A mirror contact is an auxiliary NC - 3RT10 3., 3RT13 3.<br />
Yes, acc. to <strong>EN</strong> 60947-4-1, Appendix F<br />
contact that cannot be closed simul- (removable auxiliary switch block)<br />
taneously with a NO main contact.<br />
- 3RT10 3., 3RT13 3.<br />
(non-removable auxiliary switch<br />
block)<br />
Acc. to SUVA requirements on request.<br />
Permissible ambient temperature During operation °C -25 ... +60<br />
During storage °C -55 ... +80<br />
Degree of protection acc. to <strong>EN</strong> 60947-1, Appendix C<br />
IP20 (terminal compartment IP00),<br />
AC coil assembly IP40,<br />
DC coil assembly IP30<br />
Touch protection acc. to <strong>EN</strong> 50274<br />
Shock resistance<br />
Finger-safe<br />
Rectangular pulse AC and DC operation g/ms 10/5 and 5/10<br />
Sine pulse AC and DC operation g/ms 15/5 and 8/10<br />
Conductor cross-sections<br />
2)<br />
1)<br />
For endurance of the main contacts see page 3/19.<br />
2)<br />
For conductor cross-sections see page 3/32.<br />
360°<br />
5 * " % % =<br />
NSB0_00478b