Contactors Type 3RT19 26-2P.<br />

Pneumatic delay block 1)<br />

General data<br />

Mechanical endurance Operating<br />

cycles<br />

Electrical endurance at I e<br />

Rated insulation voltage U i<br />

(degree of pollution 3)<br />

Permissible ambient temperature<br />

1) For size S0.<br />

In addition to the pneumatic delay block, no other auxiliary contacts are<br />

permitted.<br />

Accessories and Spare Parts<br />

For 3RT, 3RH Contactors and Contactor Relays<br />

Accessories for 3RT, 3RH contactors<br />

and contactor relays<br />

Operating<br />

cycles<br />

V 690<br />

5 million<br />

1 million<br />

During operation °C -25 ... +60<br />

During storage<br />

Rated operational currents Ie Acc. to utilization categories <strong>EN</strong> 60947<br />

°C -50 ... +80<br />

AC-12 A 10<br />

AC-15/AC-14 at Ue Up to 230/220 V A<br />

400/380 V A<br />

6<br />

4<br />

500 V A 2.5<br />

690/660 V A 1.5<br />

DC-13 at Ue 24 V A<br />

48 V A<br />

4<br />

2<br />

110 V A 0.7<br />

220 V A 0.3<br />

Conductor cross-sections<br />

440 V A 0.15<br />

Solid, stranded: mm 2<br />

2 x 0.5 ... 2.5 2) or 2 x 2.5 ... 4 2)<br />

Finely stranded with end sleeve mm² 2 x 0.5 ... 2.5<br />

AWG cables AWG 2 x 22 ... 12<br />

Tightening torque of the terminal screws<br />

Time delay<br />

Nm 0.8 ... 1.1<br />

Accuracy ±10 %<br />

s and u rated data<br />

Rated voltage V AC 600<br />

Switching capacity A 600, Q 600<br />

Versions<br />

Connection modules for contactors with screw terminals<br />

2) If two different conductor cross-sections are connected to one clamping<br />

point, both cross-sections must lie in the range specified. If identical crosssections<br />

are used, this restriction does not apply.<br />

3RT1900-4RE01<br />

plugs S00, S0<br />

General data<br />

Mechanical endurance Operating<br />

cycles<br />

10 million<br />

Electrical endurance at Ie Operating<br />

cycles<br />

1 million<br />

Rated operational voltage Ue V 440<br />

Rated insulation voltage U i<br />

(degree of pollution 3)<br />

Rated impulse withstand voltage U imp<br />

(degree of pollution 3)<br />

Protective separation acc. to <strong>EN</strong> 60947-1<br />

(degree of pollution 3)<br />

Rated operational current I e<br />

AC-3 at 400 V<br />

V 690<br />

kV 6<br />

V 400<br />

Rated frequency f Hz 50/60<br />

For AC operation<br />

Permissible ambient temperature<br />

During operation °C -25 ... +60<br />

During storage °C<br />

-50 ... +80<br />

Degree of protection acc. to <strong>EN</strong> 60529 IP20<br />

Conductor cross-sections<br />

Screw terminals<br />

Solid mm 2<br />

© Siemens AG <strong>2009</strong><br />

3RT1916-4RD01<br />

adapters S00<br />

A 25 20 25<br />

1x (0.5 ... 6)<br />

Finely stranded without/with end sleeve mm² 1x (0.5 ... 6)<br />

Stranded mm² 1x (0.5 ... 6)<br />

AWG cables, solid or stranded AWG 1x (20 ... 10)<br />

Tightening torque Nm 0.6 ... 0.8<br />

Corresponding opening tool Short-slot screwdriver PZ2<br />

3RT1926-4RD01<br />

adapters S0<br />

Siemens LV 1 T · <strong>2009</strong><br />