Checklists, notes<br />
9.2 Checklist for commissioning<br />
Checklist for commissioning<br />
Table 9-2 Checklist for commissioning<br />
Points to be checked<br />
Correct installation of the system<br />
Installation in accordance with stipulations<br />
Control functions and speed monitoring in accordance with stipulations<br />
o.k. Comments<br />
Light-load operation ( I < 0.5 IN, measures carried out?) Yes<br />
No<br />
Proper installation and alignment of the <strong>motor</strong><br />
Drive elements in accordance with stipulations (axial position,<br />
alignment and balancing of couplings, etc.)<br />
Compliance with minimum insulation resistances<br />
Motor connected up corresponding to the specified direction of<br />
rotation.<br />
Grounding and equipotential bonding connections correctly made.<br />
Rotor can be spun without coming into contact with the stator<br />
Flow of cooling air not impeded.<br />
Carbon brushes and brush arms freely moveable<br />
Uniform spring pressure of all brush holders<br />
All mounting screws, connecting elements and electrical connections<br />
are tight.<br />
Bearings relubricated<br />
Bearing insulation not bridged<br />
Supplementary devices and equipment (temperature monitoring, anticondensation<br />
heating, etc.) connected and functioning<br />
All shock-protection and guard measures for moving or live parts have<br />
been taken<br />
If the second shaft end has not been used, its featherkey has been<br />
secured to prevent it being thrown out<br />
Any separately driven fans are ready for operation and have been<br />
connected such that they rotate in the direction specified<br />
Any brakes fitted have been checked for proper functioning<br />
If air-to-water closed-circuit cooling is fitted: is the water cooler<br />
connected, filled, vented and ready for operation<br />
In the case of a long period between installation and start-up: test run<br />
without water cooling carried out.<br />
Comments:<br />
Date Name Signature<br />
[ID 556]<br />
SIEMENS AG T61160347010001 (DMHO V9)<br />
9-2 Operating instructions 1GG6286-0NA4.-1VV1-Z