DC motor - Siemens, s.r.o.
DC motor - Siemens, s.r.o.
DC motor - Siemens, s.r.o.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Installation and Assembly<br />
see also<br />
•= cable/conductor routings are suitable with regard to the degree of protection,<br />
type of cable routing, permissible cable diameter etc., and have been mounted<br />
in full compliance with the specifications and regulations.<br />
•= in the case of a U-shaped box frame, the associated entry plate is aligned and<br />
screwed down in such a way that the seating for the seal of the box cover is<br />
stepless all the way around.<br />
Finally close the terminal box.<br />
The tightening torque for the cover fixing screw is 22 Nm.<br />
Note<br />
Equipotential bonding is established via the fixing screws for the terminal box<br />
cover. The contact points under the screw heads are bare and protected against<br />
corrosion.<br />
Note<br />
The insulation resistance of the windings must be checked before the <strong>motor</strong> is put<br />
into operation for the first time and after a lengthy period of storage or standstill.<br />
[ID 535]<br />
<br />
Checking the insulation resistance [→ Page 4-3]<br />
SIEMENS AG T61160347010001 (DMHO V9)<br />
3-16 Operating instructions 1GG6286-0NA4.-1VV1-Z