Installation and Assembly<br />

[ID 532]<br />

3.5.6 Internal equipotential bonding<br />

General<br />

The equipotential bonding between the protective-conductor terminal in the<br />

terminal box and the <strong>motor</strong> housing is established via the terminal box fixing<br />

screws. These screws are dimensioned and designed as an "equal-conductance<br />

connection" in relation to the protective-conductor cross-section assigned to the<br />

supply-cable conductor in accordance with DIN VDE 0530 Part 1 (IEC 60034-1).<br />

Equipotential bonding<br />

In order to ensure the current carrying capacity of the connection via the fixing<br />

screws for the eventuality of a short-circuit, the following conditions must be<br />

observed:<br />

•= always use only original seals.<br />

•= the contact points under the screw heads or under the spring washers must be<br />

bare and protected against corrosion.<br />

The standard terminal box cover mounting screws are adequate as a potential<br />

bonding connection between the terminal box cover and terminal box itself.<br />

Note<br />

When carrying out installation work, take care that all equipotential bonding<br />

connections remain effective.<br />

[ID 533]<br />

3.5.7 Connection to the power converter<br />

General<br />

The ratings specified on the rating plate must be observed for operation when<br />

connected to a power converter.<br />

Converter operation on a grounded-neutral system<br />

Caution<br />

When operating with a converter with current limiting without ground-fault<br />

detection, protective-conductor currents up to 1.7 times the phase current can<br />

occur in the event of a ground fault on the output side. Neither the PE conductors<br />

of normally rated multi-core connecting cables nor the PE connecting points of<br />

normal terminal boxes are suitable for this purpose. In this case it is necessary to<br />

install an adequately rated parallel protective conductor, which must be connected<br />

to the grounding terminal located on the <strong>motor</strong> housing. Use the supplied screws<br />

SIEMENS AG T61160347010001 (DMHO V9)<br />

3-14 Operating instructions 1GG6286-0NA4.-1VV1-Z