Installation and Assembly<br />
[ID 532]<br />
3.5.6 Internal equipotential bonding<br />
General<br />
The equipotential bonding between the protective-conductor terminal in the<br />
terminal box and the <strong>motor</strong> housing is established via the terminal box fixing<br />
screws. These screws are dimensioned and designed as an "equal-conductance<br />
connection" in relation to the protective-conductor cross-section assigned to the<br />
supply-cable conductor in accordance with DIN VDE 0530 Part 1 (IEC 60034-1).<br />
Equipotential bonding<br />
In order to ensure the current carrying capacity of the connection via the fixing<br />
screws for the eventuality of a short-circuit, the following conditions must be<br />
observed:<br />
•= always use only original seals.<br />
•= the contact points under the screw heads or under the spring washers must be<br />
bare and protected against corrosion.<br />
The standard terminal box cover mounting screws are adequate as a potential<br />
bonding connection between the terminal box cover and terminal box itself.<br />
Note<br />
When carrying out installation work, take care that all equipotential bonding<br />
connections remain effective.<br />
[ID 533]<br />
3.5.7 Connection to the power converter<br />
General<br />
The ratings specified on the rating plate must be observed for operation when<br />
connected to a power converter.<br />
Converter operation on a grounded-neutral system<br />
Caution<br />
When operating with a converter with current limiting without ground-fault<br />
detection, protective-conductor currents up to 1.7 times the phase current can<br />
occur in the event of a ground fault on the output side. Neither the PE conductors<br />
of normally rated multi-core connecting cables nor the PE connecting points of<br />
normal terminal boxes are suitable for this purpose. In this case it is necessary to<br />
install an adequately rated parallel protective conductor, which must be connected<br />
to the grounding terminal located on the <strong>motor</strong> housing. Use the supplied screws<br />
SIEMENS AG T61160347010001 (DMHO V9)<br />
3-14 Operating instructions 1GG6286-0NA4.-1VV1-Z