Installation and Assembly<br />
3.5.2 Cable routing<br />
Cable entry and routing<br />
The unscrewable entry plate is supplied as standard without holes drilled so that<br />
the design, number and size of the cable glands can be adapted to the chosen line<br />
conditions.<br />
Cable entry components must:<br />
•= be adapted to the cable diameter and cable type.<br />
•= ensure degree of protection IP 55 (also applies to the screw-in point; use<br />
sealing washer and bonding).<br />
•= conform to the routing conditions (strain relief devices if cables are not fixed).<br />
Connecting cables and in particular protective conductors should be installed in an<br />
open arrangement in the terminal box and if possible with excess length in order to<br />
avoid chafing of the cable insulation.<br />
Unused cable entry holes must be sealed accordingly, ensuring that:<br />
•= the seals consist of resistant, approved material.<br />
•= the degree of protection is ensured (use sealing washer or bonding).<br />
•= they can only be opened with a tool.<br />
Note<br />
Unused cable entry holes must always be sealed with suitable sealing inserts.<br />
[ID 529]<br />
3.5.3 Connecting the ground conductor<br />
Overview<br />
The <strong>motor</strong>'s ground conductor cross-section must comply with the regulations for<br />
electrical installations (e.g. IEC/EN 60204-1).<br />
There is a hexagon bolt with flat and spring washer on the stator frame at the<br />
designated connecting point for the ground conductor. This is suitable to connect<br />
multi-core conductors with cable lugs or straps with appropriate conductor ends.<br />
When making connections, ensure that<br />
•= the contact surface is clean and bright, and is protected with a suitable anticorrosion<br />
agent, e. g. acid-free Vaseline.<br />
•= the flat and spring washers are located under the bolt head.<br />
•= the maximum permissible clamping thickness for the cable lug or strap of 10<br />
mm is not exceeded.<br />
SIEMENS AG T61160347010001 (DMHO V9)<br />
3-10 Operating instructions 1GG6286-0NA4.-1VV1-Z