3.3 Aligning<br />
Instructions relevant for safety<br />
Installation and Assembly<br />
Detailed specialist know-how is required about the necessary measures in order to<br />
correctly align and securely mount the equipment, e.g. for<br />
•= preparing the foundation,<br />
•= selecting and mounting the coupling,<br />
•= measuring the concentricity and axial eccentricity tolerances,<br />
•= axial and horizontal positioning.<br />
If personnel are not familiar with the necessary measures and working steps, we<br />
recommend that the services of the local SIEMENS service center are used.<br />
Vertical and horizontal position<br />
3.4 Mounting<br />
Mounting<br />
The following measures are required in order to compensate any radial offset at<br />
the coupling and to horizontally adjust the electric <strong>motor</strong> with respect to the driven<br />
load:<br />
•= Place shims under the <strong>motor</strong> feet to position it vertically and to avoid<br />
stressing/distorting the machines. The number of shims should be kept as low<br />
as possible i.e. stack as few as possible.<br />
•= To horizontally position the machine, push it laterally on the foundation and<br />
ensure that the axial position is maintained.<br />
•= When positioning the <strong>motor</strong>, ensure that there is a uniform axial gap around the<br />
coupling.<br />
[ID 526]<br />
Prerequisites for smooth, vibration-free running:<br />
•= Stable foundation design or stable machine suspension if flange-mounted.<br />
•= Precise alignment of the <strong>motor</strong>.<br />
•= Correct balancing of the parts to be mounted on the shaft end.<br />
To securely mount the <strong>motor</strong> and transfer the drive torque, use <strong>motor</strong> mounting<br />
bolts with the required strength class in accordance with ISO 898-1, e.g. 10.9.<br />
Note on different designs<br />
In the case of <strong>motor</strong>s with the shaft end facing upwards, it must be ensured that no<br />
water is able to enter the top bearing. Motors that are attached by their mounting<br />
feet to the wall because of their design must be supported from below by a wall<br />
SIEMENS AG T61160347010001 (DMHO V9)<br />
Operating instructions 1GG6286-0NA4.-1VV1-Z 3-7