3. Section-500<br />
3. The primer should be sprayed uni<strong>for</strong>mly over the dry surface of absorbent granular base, using<br />
suitable bitumen pressure distributor or sprayer capable of spraying primer at specified rates and<br />
temperature so as to provide a uni<strong>for</strong>mly unbroken spread of primer. Normal temperature range<br />
of spraying emulsion should be 20°C to 60°C. The rate of application depends upon the porosity<br />
characteristics of the surface to be primed and is given in Table 502.1<br />
TABLE 502.1: RATE OF APPLICATION OF BITUMINOUS EMULSION FOR PRIME COAT<br />
Porosity Type of surface Viscosity at 60°C Rate of<br />
Kinematic Saybolt Furol application per<br />
Viscosity<br />
(Centistokes)<br />
(seconds) 10 sq m(kg)<br />
Low WMM/ WBM 30 – 60 14 –28 6 – 9<br />
Medium Cement stabilized 70 – 140 33 – 66 9–12<br />
soil base<br />
High Gravel base 250 – 500 117 - 234 12- 15<br />
4. A very thin layer of coarse sand may be applied to the surface of the primer to prevent it from<br />
getting picked up under the wheels of vehicles delivering materials <strong>for</strong> construction of bituminous<br />
layer<br />
5. The surface should be allowed to cure preferably <strong>for</strong> 24 hours. Unabsorbed primer should be<br />
blotted with sand using the minimum quantity possible.<br />
B. <strong>Quality</strong> Control Requirements<br />
1. The viscosity requirements <strong>for</strong> bitumen emulsion will depend upon the type of surface as already<br />
given in Table 502.1.<br />
2. A priming grade bitumen emulsion (slow setting ) con<strong>for</strong>ming to IS:8887 should be used.<br />
3. <strong>Quality</strong> Control Tests:<br />
3.1 Tests Prior to Construction<br />
The quality control tests to be carried out prior to construction are indicated in Table 502.2. These<br />
tests shall be carried out on the bitumen binders (Emulsion/Cutback) brought on the site by the<br />
Contractor <strong>for</strong> use in the work.<br />
TABLE 502.2: QUALITY CONTROL TESTS PRIOR TO CONSTRUCTION<br />
Type of Test Frequency<br />
1. Viscosity (using Saybolt Furol Viscometer) (IS:8887) One test <strong>for</strong> each lot<br />
2. Residue on 600 micron sieve (IS:8887) -do-<br />
3. Storage Stability Test (IS:8887) -do-<br />
4. Flash Point Test, where bituminous cutback is to be used (IS:217) -do-<br />
5. Viscosity Test (IS:217), where bituminous cutback is to be used -do-<br />
86