3-10<br />

To connect to sense inputs<br />

1. Determine the required terminal and jumper blocks, and then set the<br />

jumpers for the sense inputs.<br />

a. Use the following terminal and jumper blocks for each sense input:<br />

Sense Input Terminal Block Jumper Block<br />

1 J1 J5<br />

2 J2 J6<br />

3 J3 J7<br />

b. Set the jumpers for the voltage levels for the sense inputs as follows:<br />

For this voltage Set jumper pins<br />

5V to 14V jumper pins 1 and 2<br />

14V to 24V jumper pins 2 and 3.<br />

2. Connect the external sense input device to posts 4 and 5 of the appropriate<br />

terminal block. The switch mechanism on each device should normally be<br />

open. Use the following diagram as a guide.<br />

Sample Sense Input Application<br />

Input Range Selection<br />

Jumper Block<br />

Terminal<br />

Block<br />

Normally Open Door<br />

Sense Switch<br />

330 1200<br />

1 2 3<br />

1 2 3<br />

Secondary circuit of no<br />

more than 24 VDC or VAC<br />

and no more than 60 mA.<br />

4 5<br />

Optical<br />

Isolator<br />

For 5-14V input, jumper pins 1 and 2.<br />

For 14-24V input, jumper pins 2 and 3.<br />

<strong>9560</strong><br />

External<br />

<strong>9560</strong>-03U