Erection/laying/hoisting, fitting and fixing of D.I. Pipes specials and valves of<br />

various sizes including embedding in R.C.C. floor or wall of over head reservoirs or<br />

at ground level where ever necessary, excavation of pipe line trenches, providing<br />

necessary supports and staging including supply of all jointing materials required<br />

for flange or joints.<br />

All R.C.C. works shall be finished perfectly smooth and no plastering shall be<br />

allowed except in the inside surface of walls and floors which shall be finished with<br />

a coat of epoxy paint & cement punning with water proof compound over 20mm<br />

thick cement plaster in cement mortar (1:3).<br />

All exposed faces of the concrete and plaster over masonry shall be<br />

given two coats of waterproofing cement paint of approved shade.<br />

All exposed iron works outside the reservoir shall be painted with two<br />

coats of approved synthetic enamel paint. All exposed iron works<br />

inside the reservoir shall be essentially stainless steel of suitable<br />

grade.<br />

All masonry works shall be plastered with 12mm thick cement plaster<br />

in 1:6 cement mortar.<br />

25.5 Design criteria & specification.<br />

Capacity: Capacity of the tank shall be the volume of water it can restore between<br />

the designed full supply level and lowest supply level (that is, the level of the lip of<br />

the outlet pipe). Due allowance shall be made for plastering the tank from inside if<br />

any when calculating the capacity of tank.<br />

Height of staging: Height of staging is the difference between the lowest supply<br />

level of tank and the average ground level at the tank site.<br />

Water depth: Water depth in tank shall be difference of level between lowest<br />

supply level and full supply level of the tank.<br />

Free board: Free board shall be minimum 500mm.<br />

Dead storage: Minimum dead storage of 80mm shall be assured for that bottom<br />

reservoir.<br />

Design: Before taking up the design, the designer should first decide the most<br />

suitable type of staging of tanks and correct estimation of loads including statistical<br />

equilibrium of structure particularly in regard to overturning of overhanging<br />

members shall be made. The design should be based on the worst possible<br />

combination of loads, moments and shears arising from vertical loads and<br />

horizontal loads acting in any direction when the tank is full as well as empty.<br />