Sterilisation : For sterilisation of the filtrate, chlorination with chlorine solution is<br />

used.<br />

The details of existing installations for all the six filters of 34.05 Mgd water<br />

treatment plant are indicated below:<br />

1. Raw water.<br />

i) 600mm G.I. Flanged tail piece grouted into stilling chamber. 1 no.<br />

ii) Flow meter comprising Mahindra Flow Transmitter having local<br />

mechanically operated dial indicator and remote reading indicator<br />

recorder and continuous integrator, remote instruments located in the<br />

annunciator panel in the chemical house. 1 set<br />

iii) MS shutter for shutting off flow to flash mixer and bypassing raw<br />

water to filter inlet channel direct. 2 nos.<br />

2. Chemical equipment<br />

i) Alum agitator paddle of hardwood mounted on MS vertical shaft<br />

suspended from gear box and rotating below in a GM bush grouted<br />

into alum tank floor. Shaft driven through gearing by electric motor,<br />

complete with starter. The details are : 2 sets<br />

iii) 50mm C.I. rubber lined diaphragm valve for solution and sludge. 4 nos.<br />

iv) PVC header pipe interconnecting solution outlets and connected<br />

through PVC piping or rubber hose to dosing tank. 1 range<br />

v) PVC header pipe interconnecting sludge outlets and connected<br />

through PVC piping or rubber hose to drain. 1 range<br />

vi) Stainless steel 50mm inlet float valve with PVC float and adjustable<br />

stem for maintaining a constant level in the dosing tank at any preset<br />

head 2 nos.<br />

vii) Stainless steel taper needle valve operation by a float to adjust dosage<br />

proportionate to raw water flow rate automatically. 2 nos.<br />

viii) Lining of wetted surface of alum tank and alum dosing tank with<br />

chlorinated rubber paint or bitumen. 1 item.<br />

ix) Lime agitator paddle of MS arms mounted on a horizontal MS shaft<br />

and fitted with hardwood paddle blades and lime lifting cups 1 set.<br />

x) Lime agitator drive comprising electric motor with starter, coupled<br />

through speed reducing gear-box to paddle shaft. Shaft provide with<br />

stuffing box at wall entry point. The details are: 1 set.<br />

DTS : Detailed Tender Specification. Page 233