Miscellaneous electrical safety devices/articles :<br />

Following articles/devices of appropriate quantity shall be provided and fixed in<br />

strategic locations adjacent to the main electrical installations for safety in operation<br />

and maintenance of the plant as per IE (Indian Electricity) rules.<br />

(a) EI Danger Board for 415 V AC supply system.<br />

(b) Approved type shock treatment chart to be fixed on wall.<br />

(c) Approved quality First Aid Box (Aluminum body).<br />

(d) Rubber mat of 0.415/6 KV grade.<br />

(e) Rubber hand gables.<br />

Installation :<br />

Installation work shall be carried out in accordance with good engineering practices<br />

and also manufacturer's instructions/ recommendations where the same are available.<br />

Equipment shall be installed in a neat workmanlike manner so that it is level, plumb,<br />

square and properly aligned and oriented.<br />

Lighting Fixtures :<br />

Continuous rows of fluorescent tubes shall be mounted on a continuous M.S. angle<br />

for each row of lights.<br />

Fixtures shall be mounted to maintain sufficient clearance from the overhead<br />

traveling crane trolley, if there be any.<br />

If a roof over platform is available, the fixture can be pendant mounted.<br />

Flood lights shall be mounted on steel base. Fixing holes shall be provided with slot<br />

to turn the fixture about 5 Deg on both sides. Bolts shall be finally tightened with<br />

spring washer. Terminal connection to the flood light shall be made through PVC<br />

coated flexible conduits.<br />

The fixtures after erection shall be marked up indelibly with corresponding circuit<br />

number for easy identification of lamp circuit.<br />

DTS : Detailed Tender Specification. Page 215