Junction Boxes, Conduits and Accessories.<br />

Junction box shall be of 16 SWG sheet steel, hot-dip galvanized, dust and dampproof,<br />

generally conforming to IP55.<br />

Junction box shall be complete with gasketted inspection cover, conduit knock<br />

out/threaded hub and terminal blocks.<br />

Conduits shall be rigid steel, hot – dip galvanished, furnished in standard length of<br />

3 m threaded at both ends. Conduits upto and including 25 mm shall be of 16 SWG<br />

and conduits above 25 mm shall be of 14 SWG. Minimum size of conduits shall be<br />

20 mm.<br />

Name Plate :<br />

Nameplates shall be furnished for identification of devices and circuits. All switches,<br />

controls and indications shall be permanently and legibly marked in English as to<br />

clearly indicate their functions.<br />

All lighting fixtures, receptacles, fans, junction boxes etc. shall be properly marked<br />

up indelibly with corresponding circuit numbers.<br />

Fire Protection Arrangement :<br />

(a) Portable hand held fire extinguishers : Portable hand held fire extinguishers shall<br />

be in accordance with the relevant IS and other local requirements. Each extinguisher<br />

shall be complete with a suitable wall fixing bracket. The final mounting / fixing<br />

shall be agreed on site.<br />

(b) Portable carbon dioxide size extinguishers : The 5 kg portable carbon dioxide fire<br />

extinguishers shall comply with IS/BS code.<br />

(c) Dry powder fire extinguishers : The 12 kg portable dry powder size extinguishers<br />

shall comply with IS/BS code.<br />

(d) Fire Bucket : The 12 liter capacity MS portable bucket shall be in accordance with<br />

relevant IS and other local requirement. The each bucket shall be complete with<br />

suitable wall fixing bracket. The final mounting/fixing shall be agreed on site.<br />