Exhaust Fan:<br />

For ensuring open ventilation, appropriate numbers of exhausts fan (300 mm size)<br />

shall have to be provided by the contractor to allow 12 (twelve) air changes per hour<br />

inside the pump house. 50% spare capacity shall also be provided.<br />

Switch & Switch Board :<br />

Switch boards/boxes located in control room and office areas shall be flush mounted<br />

type on brick wall with only the switch knob projecting outside.<br />

Switch boards/boxes shall have conduit knock outs on the sides. Adequate provision<br />

shall be made for ventilation of these boxes.<br />

All switches for lights, fans and plug points shall be piano key type unless other wise<br />

specified.<br />

Lighting switches shall be minimum 6 A rating of the type specially designing for<br />

A.C. circuit.<br />

Maintenance Equipment :<br />

For the maintenance of lighting fixtures within the plant buildings, the contractor<br />

shall also supply two (2) nos. free standing adjustable aluminium ladder, adjustable<br />

from 5m to 10 m.<br />

Lighting Cables & Wires :<br />

Lighting cables shall be heavy duty, 650/1100 volt grade, multicore stranded<br />

Aluminimum conductor, HR, PVC insulated PVC inner sheath, single round G.I wire<br />

amoured and over all PVC sheathed conforming to IS:1554. Cable size from Lighting<br />

Panel to junction box shall be minimum 10 sq. mm.<br />

Lighting wires shall be 650/1100 volt grade PVC insulated stranded conductor, single<br />

core copper wire conforming to IS:694 and colour coded, wire size from junction box<br />

to lighting fixture shall be minimum 2.5 sq. mm.<br />