Lighting Distribution Boards shall have provision of cable entry from bottom and,<br />

panels shall have provision of cable entry from top and bottom, as required, with<br />

removable gland plates. Necessary double compression type brass cable glands,<br />

tinned copper/aluminium cable lugs are to be furnished.<br />

Two ground terminals shall be provided on opposite sides of each Lighting<br />

Distribution Board and Lighting Panel for connection to ground conductor.<br />

Each MLDB and Lighting Panel shall be complete with designation and caution<br />

notice plates fixed on front cover and a directory plate fixed on inside of the front<br />

cover. This directory plate on the MLDB shall contain details of the Lighting Panels<br />

being fed from it including their designation, location, loading etc. The directory<br />

plate on the Lighting Panel shall contain details of the points to be controlled by<br />

each circuit including the location of the point controlled, rating of the protective<br />

units and loading of each circuit. The plates shall be of anodized aluminium with<br />

inscriptions indelibly etched on it.<br />

Bus bar shall be electrolytic grade hard drawn aluminium, colour coded for easy<br />

identification and designed for a maximum temperature of 85°C. Minimum rating<br />

of phase and neutral Bus Bars shall be 67% (approximately) of the total rating of<br />

fuse ways. Above 32 A, neutral Bus Bars may be half the size of phase Bus Bars.<br />

Board/Panel shall be fitted with phase barriers such that it is not readily possible for<br />

personnel to touch the phase bus bars. Insulation barriers shall preferably be fitted<br />

around the circuit breakers such that only the surface and the toggle of the circuit<br />

breaker are available on the front. Incoming and outgoing circuits shall be<br />

terminated in suitable terminal blocks.<br />

Receptacles:<br />

Receptacles shall be heavy duty, complete with individual plug. The conduit box of<br />

the receptacle shall be provided with earthing screws with washer and nuts welded<br />

on the surface for grounding with 16 SWG G.I. wire. Arrangement shall be<br />

provided inside the conduit box for grounding of third pin.<br />

Shrouded type plug shall be provided with corresponding matching arrangement at<br />

sockets to prevent accidental contact with finger during plug insertion.<br />

DTS : Detailed Tender Specification. Page 212