Fixtures shall be fully wired up to respective terminal blocks, suitable for loop-in and<br />

loop-out connection of PVC wires of following sizes:<br />

a) Lighting fixture : 2.5 mm 2 Copper<br />

b) Flood Light fixture : 2x2.5 mm 2 Copper<br />

Lamps:<br />

General lighting service (GLS) lamps shall be with clear glass and screwed caps.<br />

All fluorescent lamp shall be bi-pin rotary type and either cool daylight or white as<br />

per annexure. Lamp holder shall be spring loaded, low contact resistance type and<br />

shall have resistance to wear.<br />

Mercury/Sodium vapour lamp shall be colour corrected type with screwed cap.<br />

Lamps shall be suitable for use in position and capable of withstanding small<br />

vibrations. Restrictions and special features, if any, shall be clearly indicated in the<br />

bid.<br />

Ballast:<br />

Ballasts shall be heavy duty, low loss, polyester-filled type with copper winding.<br />

Ballast for Mercury/Sodium vapour lamp shall be provided with suitable tappings to<br />

set the voltage within range specified. Ballasts shall be free from hum. Ballasts,<br />

which produce humming sound, shall be replaced, free of cost, by the Contractor. In<br />

multi-lamp fixture, each lamp shall be provided with individual ballast. Ballast<br />

windings shall have maximum operating temperature of 120 o C without rated<br />

temperature rise marking.<br />

Lighting Panel/Distribution Boards:<br />

Lighting Distribution Boards/panels shall be totally enclosed metal clad type,<br />

fabricated from rust proof sheet steel of 16 SWG and finished with anticorrosive<br />

powder coated paint and suitable for fixing on walls/brackets.<br />

Lighting Distribution Boards and Lighting Panels shall be so constructed as to<br />

permit free access to the terminal connections and easy replacement of parts. Front<br />

access doors shall have padlocking arrangements.<br />