19.34 Illumination Level and Circuit Loading.<br />

(d) Illumination level of the pump house indoor and outdoor areas shall be designed on<br />

the basis of IS : 3646 with average minimum illumination level of 250 lux within the<br />

pump house. The outdoor area shall be provided with average illumination level of<br />

15-20 lux. 100 % spare capacity for the lighting loads and fixtures shall be provided<br />

both at the indoor and outdoor areas.<br />

(e) Voltage drop at the fixture from the MLDB bus shall not exceed 3%.<br />

(f) Circuit loading of each lighting Panel shall be done in such a way that almost<br />

balanced loading in all the three phases is achieved.<br />

(g) At least two sub circuits shall be used for illumination of a particular area.<br />

19.35 Specific Requirement.<br />

Lighting Fixtures.<br />

Lighting fixtures shall be designed for minimum glare. The surface finish shall be<br />

smooth, unobtrusive and scratch resistant.<br />

Reflector shall be of sheet steel or aluminium of minimum 20 SWG thick, securely<br />

fixed by fastening device of captive type.<br />

Fixture shall be suitable for 20 mm conduit entry and 16 SWG G.I. earth wire<br />

connection.<br />

High bay fixtures shall have provision for vibration damper to ensure rated lamp<br />

life.<br />

Fixture shall be furnished complete with lamps and integrally/not-integrally or<br />

separately mounted control gear & accessories as applicable for different types of<br />

fixtures. These shall include holders, ballast, capacitor, starter, igniters etc.<br />

DTS : Detailed Tender Specification. Page 210