Each installation shall include the distribution board, wiring, light fittings, socket<br />

outlets, exhaust fan, earthing and external flood lighting etc. as required together with<br />

all conduits, trays and accessories as necessary to complete the whole of the<br />

installations.<br />

In general, fluorescent fittings and indoor ceiling mounted High Bay Lamp shall be<br />

used for internal lighting with weather proof fittings for exterior mounting on<br />

building structures above and adjacent to the door openings.<br />

External wall mounted luminaries shall be installed using a back entry conduit system<br />

terminating behind the respective fitting with an end box mounted on the building<br />

fabric. Appropriate neoprene seals shall be used to prevent ingress of moisture. The<br />

final connections of each fitting shall be sleeved with silicon glass over sleeving.<br />

Lighting fixtures, ceiling fans, Exhaust fan and flood lights shall generally be<br />

individually controlled from the lighting panel / switch boxes. How ever the out door<br />

tub light fixture may be group control through switch boxes where each switch may<br />

control maximum 3 nos. fluorescent fixtures. For area illuminated by more then one<br />

circuit, the adjacent circuits shall be fed from different phases.<br />

19.33 Emergency D.C. lighting.<br />

In case of a total power blackout, emergency lights with rechargeable battery back up<br />

installed at strategic locations, shall give nominal illumination for safe movement and<br />

essential function.<br />

The lamps shall be 11/18 W Tungsten Halogen operated by a sealed type lead acid<br />

battery. A solid state constant voltage charger shall be provided together with low<br />

voltage cutout protection to prevent from over discharge of the battery. The units<br />

shall be suitable for the environment in which they are to operate. The emergency<br />

lighting load shall comprise at least 10% of the normal lighting load. The exact<br />

location and distribution of the fixtures shall, however, be finalized during detailed<br />

engineering stage.<br />

The power for emergency D.C. lights shall be arranged by the contractor from the<br />

plant source.<br />