The contact configuration of pressure switches shall be DPDT type for each set<br />

point/position contact rating shall be 5A/230V AC & 0.2A/220V DC minimum.<br />

Set points shall be adjustable through out the range with a calibrated scale indicator<br />

set point. Switching differential shall be adjustable.<br />

Flow meter/sensor<br />

The flow sensor is to be installed & commissioned to measure the instant rate as<br />

well as totalized flow for a period of time passing through the header pipe. The flow<br />

meter shall be electromagnetic type. The sensor shall be full bore type installed U/G<br />

in the masonry pit. One flow stabilizing pipe of length 20D at the U/S & 5D at the<br />

D/S of the flow sensor shall be provided. The minimum & maximum flow rate that<br />

the sensor can measure shall be clearly spelt out & shall match with the scheme<br />

requirement & the offered pump discharge capacity working on safe operating zone.<br />

The indicator shall read the flow rate in M 3 /hr scale & the totalizer shall indicate the<br />

total flow in M 3 . The indicator & totalizer shall be installed within the room meant<br />

for electric control and shall either be housed centrally within the LT Panel Board<br />

or in a separated wall mounted panel. The flow sensor shall be suitable for PN 1.0<br />

pressure rating. The flow sensor shall be powered as necessary from the LT Panel<br />

Board through PVC Control Cable described elsewhere. If the flow meter demand<br />

for any signal conditioner/amplifier and/or Power Converter etc. the same shall be<br />

provided with the unit. Since the sensor pit may not be 100% water proof the sensor<br />

with terminal connections shall be suitable for prolonged submergence companion<br />

flanges as per sensor unit shall be provided with the stabilizing pipes. The accuracy<br />

of the flow sensor shall be within ± 1% of the full scale. The <strong>Bid</strong>der shall submit the<br />

data sheet of the Flow meter duty filled in<br />

Alarm Annunciation System:<br />

Audio visual Alarm annunciation system shall be provided as per relevant IS<br />

specification. System shall include panel mounted facia comprising of LED array<br />

assemblies, sets of alarm accept, reset & test push buttons panel mounted audible<br />

devices etc. Facia shall be visible from a minimum distance of 3 meter.<br />

Relays:<br />

Relays shall be electro magnetic type miniature plug-in or DIN rail mounted. The<br />

coil voltage of the relays may be 240V AC/24V DC (appropriate voltage source to<br />

be arranged by the <strong>Bid</strong>der). LED shall be provided at coil for indication.<br />

The contact type of relays shall be 2 NO + 2 NC (minimum) having contact rating<br />

of 5A/230V AC and 0.25A/220V DC. Additional contact shall be provided as per<br />

requirement.<br />

DTS : Detailed Tender Specification. Page 202