Pressure gauge (IS 3624):<br />

The delivery of all the Pumps and Pump common header shall be provided with dial<br />

type pressure gauge of suitable range complete with copper tubes and control cocks.<br />

The gauges shall be of direct mounting SS diaphragm sealed type. The dial size of<br />

each pressure gauge shall not be less than 100/150 mm. The M.O.C. shall be<br />

suitable for storm/raw water pumping installation. Each pressure gauge shall be<br />

complete with snubber of suitable class of enclosure. Accuracy shall be 1 % of<br />

full scale range or better. Scale range shall be selected so that normal system<br />

pressure is approximately 50 % of the full scale.<br />

Specification:<br />

1. Quantity to be provided : 4 nos.<br />

2. Type : Top mounted (directly) diaphragm sealed type.<br />

3. Reference standard : IS 3624<br />

4. Range : 0 – 10 Kg / cm. sq<br />

5. Dial size : 100 / 150 mm.<br />

6. Accuracy : 1 %<br />

7. M.O.C.:<br />

Dial<br />

Flanges<br />

Internals<br />

:<br />

:<br />

:<br />

Cast Aluminium<br />

SS 316<br />

SS 304<br />

8. Enclosure : Weather proof IP 65.<br />

9. Accessories With M.O.C : Snubber, 2 way cock of SS 304<br />

Pressure Transmitters:<br />

Pressure Transmitters shall be 2 wires, smart type with facility for remote<br />

calibration. Transmitters shall also have 4-20 mA, DC output capacity up to 600<br />

ohms. Transmitters shall be provided with Local Digital indicator & shall generally<br />

be installed on Instrument stands made of 2 M.S. pipe at a convenient point.<br />

The sensing element material & internal parts shall be constructed with AISI316L<br />

in general.<br />

Temperature – Sensor Element.<br />

All Temperature Sensor Elements shall be of Duplex type with SS316 sheath &<br />

Mgo filled depending on temperature ranges, Pt:100 Probe, RTD or thermo conpu<br />

shall be used. Outer dia. of the sheath shall be minimum of 6 mm.<br />

Pressure & Differential Pressure Switches:<br />

Local switches for pressure, differential pressure etc. shall be blind type having<br />

potential free contact output for alarm/inter lock purposes. All switch elements shall<br />

be snap acting & shock proof type.<br />