19.16 Specification of Instrumentation.<br />

Level indication/Control System.<br />

Level indication system shall be consisting of 1 level indicator for the Intake Well<br />

common for all the Pumps. Level Control System shall be comprising of 1 float operated<br />

displacer type level switch for each pump in the Intake Well for Auto Tripping of the<br />

vertical Pumps at very low water level (preset level below the low water level) and the<br />

arrangement will be such that the pump shall not be started in case of low level at the<br />

Intake Well. To reduce the effect of water turbulence in the Intake Well, Stilling pipe shall<br />

be provided for proper functioning of the level floats for both level indication and level<br />

control system.<br />

For the Intake Well in addition to the magnetic level switch operated indicating<br />

arrangement common for all the Pumps as mentioned above, a common mechanical float<br />

operated scale board with pointer type level indicator shall be provided. The installation<br />

shall be complete with mounting nozzles and flanges, anchor bar, float, guide wires, float<br />

wire, pulley and pulley saps, counter weight, scale board and pointers etc..<br />

A) Specification of Level Indicator:<br />

1. Quantity to be provided : 1 no.<br />

2. Type : Float type mechanical level indicator complete with float<br />

and guide wire, nozzle with flange, pulley and pulley<br />

shaft counter weight, scale board with pointer etc.<br />

3. M.O.C.:<br />

Float, guide wire and guide rope.<br />

Nozzle with flame.<br />

Pulley and pulley shaft<br />

Counter weight.<br />

Scale Board.<br />

:<br />

:<br />

:<br />

:<br />

:<br />

SS 316<br />

MS, IS 2062<br />

SS 304<br />

C.I<br />

Aluminium<br />

4. Make : Levcon instruments/D.K Industries/Scientific Serve / MSI<br />

B) Specification for Buoyancy type level control switch:<br />

1. Quantity to be provided : 3 nos.<br />

2. Type : Top mounted magnetic level switch displacer operated<br />

3. Enclosure Class for switch : Weather proof, IP - 66<br />

4. No. of contacts : 2 nos., SPDT<br />

5. Switch type : Micro switch<br />

6. M.O.C.:<br />

Displacer, wire pipe, spring<br />

housing, sleeve pipe, sleeve rod<br />

Sleeve<br />

Spring<br />

Flange cage<br />

Switch box, housing<br />

:<br />

:<br />

:<br />

:<br />

:<br />

SS 304<br />

SS 410<br />

Spring Steel<br />

MS, IS - 2062<br />

Aluminium<br />

7. Current rating, Voltage : 5A, 230 V<br />

8. Stilling guide pipe (perforated) : MS, IS – 2062 (length as required to suit the wire rope)<br />