19.12 L.T. 415V, Power Distribution Panel Board<br />

The L.T, 415V, PDB shall effectively receive power & distribute to different outlet<br />

of motor control circuit and lighting etc. The L.T. 415V. PDB shall effectively<br />

receive power and distribute to lighting panels be suitable for 415v ± 10%,<br />

50 Hz ± 5%, 3 phase, 4 wire, A.C supply system. The incoming power shall be<br />

made available from the nearby 11 Kv/0.433 V transformer prior to commissioning<br />

of the station.<br />

19.13 Motor Control Centre :<br />

The Motor Control Centre shall have the following provisions:<br />

For receiving the supply : ACB or MCCB.<br />

For distribution : Bus bar, switch fuse units, circuit breakers.<br />

For controls : Starters: level-controls, if needed: Time-delay relays.<br />

For protections : Under voltage relay, over-current relay, hot fault relay, single<br />

phasing preventor.<br />

For indications and readings : Phase indicating lamps, voltmeters, ammeters,<br />

frequency meter, power factor meter, temperature scanners, indications for state of<br />

relays, indications for levels, indications of valve positions, if valves are powered<br />

actuated, indication of power pressure.<br />

The HT Panel board for motors shall be capable to provide the following<br />

signals/data to the PLC for automation/visualization.<br />

■ Voltage on either side of the bus coupler, current for each outgoing feeder,<br />

energy consumed as well as incoming frequency.<br />

■ The HT panel board should be capable for switching on/off from local (pump<br />

house) or remote (i.e. from PLC via the MMI).<br />

■ Basic information of each breaker such as breaker on/off/trip, in test/service<br />

position etc. to be informed to PLC. PLC & MMI PC system is however<br />

outside the scope of this work.<br />

■ The auxiliary supply for tripping coil/closing coil (110V DC or 220V DC)<br />

shall be built-in power pack through rectifier unit and for spring charging<br />

motor of the VCB and that of the space heater, indication etc. of the panel,<br />

external 230V power shall be supplied for external source to the built-in<br />

wiring of the panel offered.<br />

DTS : Detailed Tender Specification. Page 198