Hot thermal withstand curve shall have a margin of at least 10% over the full load<br />

current of the motor to permit relay setting using motor rated capacity.<br />

The motors subject to reverse rotation shall be designed to withstand the stress<br />

encountered when starting the non – energized shaft rotating at 125% rated speed in<br />

reverse direction.<br />

The motors shall be provided with Pt:100 type temp. detector probe at both<br />

D.E & non DE bearings with alarm & trip contacts (4 Nos. + 4 NC) and the leads of<br />

the Embedded temp. detector shall be brought out to a separate terminal box.<br />

The motors of 56.25 Kw & above shall be provided with embedded winding temp.<br />

detector to monitor & trip the motors in case of excess temp.<br />

The motors shall be smooth in operation and the noise level shall not exceed 85 db<br />

at 1.5m from the motor. The vibration level of the pump & motor shall be within the<br />

specified limit of IS : 11724.<br />

The motors above 18.75 KW shall be equipped with built in anti condensation<br />

thermostatically controlled space heater of adequate rating suitable for operation at<br />

220V, AC supply. Separate terminal box for the space heater connection are to be<br />

provided.<br />

The motors shall be provided with antifriction bearing unless sleeve bearings are<br />

required as manufacturing standard. Vertical shaft motors shall be provided with<br />

thrust & guide bearings. The bearing shall be grease lubricated both at DE & NDE<br />

and the same shall be provided with seals to prevent leakage of lubricant or entrance<br />

of foreign matter like dirt, water etc. into the bearing area.<br />

The frame of the motor shall be provided with two separate & district earthing<br />

terminals complete with tapped holes, G. I. bolts & washers for external earthing<br />

with G.I. Flat of size 40 6 mm & above.<br />

The motor terminals box shall be detachable type & located in accordance with IS<br />

clearing in motor base plate foundation. It shall have adequate space inside for<br />

terminating 3 core, 1.1Kv gd upto 95 sq. mm PVC/XLPE Al-conductor cable.<br />

Terminals shall be stud type & thoroughly insulated from frame to provide good<br />

insulation value. The terminals shall be clearly identified with markings. Direction<br />

of rotation shall be marked on the NDE of the motor. The terminal box shall be<br />

capable of withstanding max system fault current for a duration of 3.0 sec.<br />

DTS : Detailed Tender Specification. Page 196