4. Detail Particulars :<br />

The technical particulars of the motors shall be closely matched with the<br />

characteristics of the pumps. The motors shall be started with star delta starters.<br />

Other details specification of the motors shall be as follows:<br />

Duty : Continuous<br />

Rating : To be decided as per requirement of the driven equipment<br />

stipulated in the technical specification subject to min.<br />

45Kw.<br />

No. of Poles : 4<br />

Frame size : As per IS/other relevant ISO/IEC standards<br />

Mounting : Horizontal, Foot mounting (for vertical motors)<br />

Method of starting : Star/Delta<br />

Insulation of stator : Class ‘F’ with 70° temp rise over 50° ambient winding<br />

Starting Torque : 200% of FLT<br />

Pull out Torque : 250% of FLT<br />

Starting current : Shall be limited to 300% of FLC for FASD starting with<br />

100% voltage at motor terminals (subject to IS tolerance)<br />

Starting time : Shall be within 10 sec<br />

Terminal box : Suitable for PVC-Al, 3C power cables of required size.<br />

Construction : TEFC/CACA, squirrel cage.<br />

Encloser : IP:55 as per IS:4691.<br />

The motors shall deliver the rated output & accelerate the full speed with 85% of<br />

the rated voltage at the motor terminals.<br />

Each motor shall be capable of at least two cold restarts & one hot restart. The<br />

motors shall be suitable for 3 equipaced starts per hour under all operating<br />

conditions.<br />

Each motor shall be capable of withstanding the stress developed due to sudden<br />

application of 150% of rated voltage at the motor terminals during bus transfer due<br />

to phase difference between the incoming voltage & motor residual voltage.<br />

Locked rotor withstand time under hot condition at 110% rated voltage shall be<br />

more than the motor starting time by at least 5 sec. The starting time mentioned<br />

above shall be at minimum permissible voltage of 80% rated voltage.<br />

DTS : Detailed Tender Specification. Page 195