19.9 Packing for Transportation.<br />

All parts shall be properly boxed, crated or other wise protected for transportation<br />

and handling. Exposed machine finished surfaces shall be thoroughly greased<br />

before packing.<br />

The <strong>Bid</strong>der shall fill up the check list and submit with the offer.<br />

19.10 Technical specification for the drive motors.<br />

1. Codes & Standards : The motors shall be conforming to the following IS<br />

specification :<br />

IS : 325, 2223, 1231, 4691, 2540 & IEC : 34 & 72 : AC induction motor.<br />

2. Electrical System :<br />

Voltage : 6600 V, 10%<br />

Frequency : 50 HZ 5<br />

%<br />

Combined variation : 10%<br />

AC Supply<br />

System Neutral : Directly earthed<br />

3. Design & Operational requirement :<br />

The drive motor shall be squirrel cage, induction type with vertical solid shaft<br />

having a degree of protective of IP – 55 with CACA, self radial ventilation type<br />

encloser. The rating of the motors shall be selected considering the max BKW of<br />

the pumps at 6%<br />

frequency variation. As the pump is designed to develop the<br />

required pressure at a speed of 1400 Rpm corresponding to a motor speed when<br />

connected to a power system with a frequency of 47.50 Hz., the motor capacity<br />

shall have ample margin of power to take care in the event of sudden increase in the<br />

input power to pumps, when speed suddenly shoots up as a result of sudden<br />

fluctuation in the frequency of power system to the upper limit of 51.50Hz. In<br />

worst operating condition whichever is higher subject to the condition that the<br />

above rated motor shall satisfy the requirement of the pumps at all working<br />

conditions otherwise higher rating motor should be selected to satisfy the demand.<br />

Adequacy of motor power shall also be checked with the pump input power<br />

required during solo pump operation in the event of tripping of the other pump(s)<br />

operating in parallel. The motors shall be suitable for rotation in both direction.<br />