5. a) Centre to centre spacing (between 2 adjacent<br />

pumps)<br />

b) Inner diameter of the R.W. intake well : 10000 mm<br />

: Shall be limited to 1500mm<br />

c) Pump house size over the deck : 12000mm x 12000 mm<br />

6. Pump column pipe & discharge header pipe : Minimum 300mm &<br />

350mm<br />

7. Relative humidity at site : 100% (Max.)<br />

8. Average maximum ambient temperature : 25° C<br />

9. Environment of operation : Dust free/non hazardous<br />

10.<br />

Floor cut out for pump suspension lower tier of<br />

the pump deck<br />

: Shall be kept as required<br />

(for present and future – 2x<br />

3nos.)<br />

11. Delivery pipe/cable trench : Shall be kept in the floor of<br />

pump house with chequered<br />

plate.<br />

<strong>Bid</strong>der shall submit with the technical offer, the details of calculation so as to arrive<br />

at the total head of the pumps. The pump characteristic curves, the solo and or<br />

parallel operation curves of the pumps superimposed with the system head curves<br />

etc. as mentioned in the technical specifications of the pumps shall have to be<br />

furnished with the offer.<br />

The curves, drawings etc. shall be in English Version and shall contain the Logo of<br />

the respective Pump manufacturer duly signed by the authorised signatory of the<br />

same. The curves shall comprise the following: (i) Discharge, (ii) Head, NPSH,<br />

minimum submergence, (iii) Power (KW), (iv) Efficiency (%). In absence of such<br />

information, curves, drawings of the <strong>Bid</strong>ders may be considered as technically<br />

invalid and rejected.<br />

19.5 Technical specification of the vertical wet pit type pumps.<br />

Codes and Standards : The design, material, construction, manufacture,<br />

inspection, testing and performance requirement of vertical pumps shall comply<br />

with all applicable codes and standards:<br />

IS – 1710 : Vertical turbine pumps for clear, cold, fresh water<br />

IS – 5120 Technical requirements – Roto dynamic special purpose pumps<br />

IS – 9137 : Code of acceptance for centrifugal, mixed flow and axial flow pumps class “C”<br />

DTS : Detailed Tender Specification. Page 187