The pumps shall be of non pull out type. The individual pump discharge line shall<br />

run over the main operating floor and shall be connected with the common delivery<br />

header line of 3 pumps. The pump discharge head/motor stool/sole plate shall be<br />

rigidly grounded on the pump floor. The proposed foundation plan and foundation<br />

pockets are to be kept with the civil construction matching with the foundation plan<br />

of the pump -motor furnished by the pump manufacturer. The said foundation shall<br />

take care and encounter the horizontal back thrust as may generate during start/stop<br />

condition, for which maximum of its value i.e. at the maximum H.W.L. should be<br />

considered.<br />

Tentative foundation plan of the pump, motor, discharge head and sole plate,<br />

common manifold with individual pump discharge pipes etc. are shown in the<br />

layout drawing. The <strong>Bid</strong>der shall furnish the details of the foundation of the pump<br />

motor sets from the pump manufacturer. The foundation pockets of the pump-motor<br />

sets are to be constructed in the civil works matching with the foundation details to<br />

be had from the pump manufacture within the terms of the contract. Similarly the<br />

equipment load data as may be required for civil construction shall also be arranged<br />

by the contractor from the pump manufacturer. The offered pumps motors and other<br />

equipments shall match the stated requirements (foundation plan, total available<br />

floor area, minimum height of crane with minimum hook clearance over floor etc.)<br />

as shown in the layout drawing and a line of confirmation for the same shall be<br />

furnished with the technical offer.<br />

The pump shall be with below surface discharge and the pump discharge<br />

head/motor stool, thrust bearing housing and sole plate shall be of suitable of design<br />

and construction to act as encountering device for the pump back thrust. Individual<br />

pump discharge branch shall include DF, Rubber Expansion joint, Non Return<br />

Valve and motorized Butterfly valve, discharge piping etc.<br />

The H.T/L.T. Power, control and signal cables from the respective switch/breaker/<br />

electrical outlets shall be partially within metallic tray/hangers in the pump house<br />

enclosure. All cable laying, supply, fixing of cable trays/hangers as required shall<br />

lie in the scope of this job.<br />

The <strong>Bid</strong>der shall also furnish the details of foundation of the electrical Panel Board,<br />

pipes, valves and special etc. The <strong>Bid</strong>ders are advised to give a confirmation on<br />

clear term that the layouts are acceptable to them fulfilling all technical<br />

requirements of their offered equipments. The equipment layout details, data etc.<br />

are to be clearly incorporated in the layout drawings by the <strong>Bid</strong>ders and are to be<br />

submitted along with the offer.<br />

DTS : Detailed Tender Specification. Page 185