Motor starting arrangements:<br />

Individual Motor starters/panels for 415 volt 3 Phase 50 Hz Motors shall be as<br />

below:-<br />

For Squirrel cage motors up to 3.7 kW : Direct-on-line<br />

Squirrel cage motors above 3.7 kW to 38kW : Star-delta starters<br />

For motors above 38kW to 75kW : Auto transformer<br />

For motors above 75kW : FCMA Starters<br />

Each control panel/starter shall incorporate isolator, HRC fuse conductors, timing<br />

relays, overload relays, single phase preventor, Hour meter (for pump running<br />

hours) etc. appropriate for the scheme of control. Contactor rating for each motor<br />

shall be at least 25% higher than the full load current of the motor and contactor<br />

shall comply with the requirements of IS:13947 Part:4 Sec-1 and IS:10118.<br />

Reversible starters shall be provided wherever necessary.<br />

GTS : General Technical Specification. Page 156