Base plate:<br />

The common base plate for pump and motor shall be fabricated from mild steel<br />

sections and have sufficient rigidity to resist vibration and distortion. Suitable holes<br />

shall be provided for grouping and they shall be so located that the base will be able<br />

to be grouped in place, without disturbing the pump and motor. The base plate<br />

should be of the drain rim type to collect any gland water leakage and lead to drain.<br />

All pumps and motors shall be properly and accurately aligned, bolted and doweled<br />

to the base plate. Adequate space shall be provided between pump drain<br />

connections and base plate for installation of minimum 15 mm diameter drain pipe.<br />

Foundation bolts shall be complete with nuts and flat and shake proof washers.<br />

Coupling:<br />

A flexible pin bush type coupling shall be provided, duly bored and keyed to the<br />

pump and motor shafts.<br />

The coupling and the pump shafts have to be designed that the breaking load of the<br />

coupling system is below that of the shaft.<br />

Accessories:<br />

All specified accessories and any other standard accessories required for correct and<br />

safe operation of the pump shall be furnished with the pumps. All incidental piping<br />

(including valves) required for sealing, lubrication and cooling of stuffing box<br />

packing and/or pump bearing shall be furnished by the contractor. A mild steel<br />

fabricated coupling guard shall be provided to rotating parts of the pump and motor.<br />

Eye bolts (as many per pump as required) shall be provided for ease of lifting and<br />

installation.<br />

The pump shall be fitted with a suitable vent connection at the top.<br />

All the liquid passages in the casing and impeller, which are inaccessible to<br />

machining finish, shall be finished to a smooth surface as far as is possible.<br />

Drawings and information to be provided.<br />