The pumps shall be capable of reverse rotation up to 125% rated full speed of the<br />

drive motor, due to backflow of water, without damage or loosening of threaded<br />

components.<br />

The first critical speed shall be away from the operating speed and in no case less<br />

than 130% of the rated speed.<br />

Though the specifications for flanges are mentioned elsewhere in this document, it<br />

is contractor's responsibility to ensure that correct matching flanges are provided<br />

with the pump.<br />

Spare parts supplied with the pump shall be identical to respective pump<br />

components and shall be from original manufacturer.<br />

Pumps shall run smooth without undue noise or vibration. Noise levels and<br />

amplitude of vibrations shall be within acceptable limits. Noise level shall be<br />

limited to 85 db at a distance of 2 m. and amplitude of vibrations (peak to peak)<br />

shall be within 2.5 MILS in any plane as per relevant hydraulic institutes’ standards<br />

and IS.<br />

Unless otherwise specified, drive unit power rating shall be the maximum of the<br />

following requirements.<br />

a) 15% margin over the pump shaft input power at the rated duty point.<br />

b) Pump shaft input power required considering the overloading of the pump, if any,<br />

assuming single pump operation in the event of tripping of one or more of the pumps<br />

operating in parallel.<br />

c) Maximum pump shaft input power required for operation of pump at any point on the<br />

pump performance curve between pump shut off and pump run out condition.<br />

The pump characteristics of the offered pump should be such that shut off head is at<br />

least 15% more than the design head.<br />

Pumps shall be identical and shall be suitable for parallel operation with equal load<br />

division.<br />

GTS : General Technical Specification. Page 148