Suppression of Noise:<br />

All plant offered shall be quiet in operation. The noise levels in the entire premises<br />

shall be as per the norms of the Pollution Control Board. The noise levels measured<br />

as per IS/ISO:4412-1, 2-1991 shall be within the levels prescribed by MSPCB. The<br />

noise level within the building shall not be more than 85 decibels (+5 per cent on<br />

this over the audible frequency spectrum measured at mid-band.) “A” scale when<br />

measured along a contour 3 metres from any single item of plant during starting,<br />

running and stopping. The noise level outside the building shall not be more than<br />

60 decibels (+5 per cent on this over the audible frequency spectrum measured at<br />

mid-band.) “A” scale when measured along a contour 3 metres from the external<br />

wall. Noise test measurements shall be made on completion of the installation of<br />

the plant at Site to verify that it complies with this Clause. Plant which fails to<br />

comply with the noise level limits when tested will render it liable for rejection<br />

unless it is satisfactorily modified at the Contractors expense by the programmed<br />

commissioning date.<br />

15.23 Horizontal Split Casing Centrifugal Pumps (Water).<br />

General:<br />

This section covers in general the required specification with respect to horizontal<br />

split casing centrifugal water pumps. The details pertaining to the design, drawing,<br />

selection of equipment/materials, procurement, manufacture, installation, testing &<br />

commissioning however if not mentioned, the same shall be of high standard of<br />

engineering and shall comply with all currently applicable standards regulation and<br />

safety codes.<br />

System Head Curves:<br />

The pump shall be suitable for operation in a pumping system, at the duty points<br />

specified for each pump and should be able to satisfactorily operate within the range<br />

of operation indicated on the system resistance curve or as specified.<br />

GTS : General Technical Specification. Page 146