The capacitor bank may comprise of suitable number of single phase units in series<br />

parallel combination. However, the number of parallel units in each of the series<br />

racks shall be such that failure of one unit shall not create an over voltage on the<br />

units in parallel with it, which will result in the failure of the parallel units.<br />

The assembly of the banks shall be such that it provides sufficient ventilation for<br />

each unit. Each capacitor case and the cubicle shall be earthed to a separate earth<br />

bus.<br />

Each capacitor unit/bank shall be fitted with directly connected continuously rated,<br />

low loss discharge device to discharge the capacitors to reduce the voltage to<br />

50 volts within one minute in accordance with the provisions of the latest edition of<br />

IS :13585 Part 1.<br />

Film dielectric, Aluminium foil conductor, impregnated with Non PCB, Non Toxic<br />

biodegradable capacitor grade oil, under vacuum, two layers of biaxially oriented<br />

propylene film shall be used.<br />

Each unit shall satisfactorily operate at 135% of rated kVAR including factors of<br />

over voltage, harmonic currents and manufacturing tolerance. The units shall be<br />

capable of continuously withstanding satisfactorily any over voltage upto a<br />

maximum of 10% above the rated voltage, excluding transients.<br />

Unit Protection:<br />

Each capacitor unit shall be individually protected by an MCCB/MCB fuse suitably<br />

rated for load current and interrupting capacity, so that a faulty capacitor unit shall<br />

be disconnected by the fuse without causing the bank to be disconnected. Thus, the<br />

fuse shall disconnect only the faulty unit and shall leave the rest of the units<br />

undisturbed. An operated fuse shall give visual indication so that it may be detected<br />

during periodic inspection. The MCB breaking time shall co-ordinate with the<br />

pressure built up within the unit to avoid explosion. Mounting of the individual<br />

fuse may be internal or external to the capacitor case.<br />

Capacitor Control Panel:<br />

The control equipment shall be mounted in the MV panel made of 2.6mm/2.0mm<br />

cold rolled sheet steel for the front and other sides respectively. The panel shall be<br />

of indoor type and shall consist of :<br />

- Isolating switch/MCB/MCCB<br />

- Red and Green lamps for capacitors ON/OFF indication.<br />

GTS : General Technical Specification. Page 135