Sizes of earthing conductors:<br />

Sl.<br />

System Earthing conductor size and<br />

No.<br />

Material<br />

1 2 3<br />

1 415V switchgear, DG set, Capacitor Control<br />

panel<br />

2<br />

415V LT Motors<br />

Suitable to its rating.<br />

- less than 50 HP 25 x 6 mm GI<br />

- 50 - 150 HP 40 x 6 mm GI<br />

- above 150 HP 50 x 6 mm GI<br />

3 Lighting distribution Board, 14 SWG GS wire<br />

4 Local push Button Stations, Junction Boxes. 14 SWG GS wire<br />

5 Lighting and receptacle system 14 SWG GS wire<br />

6 Earth Electrode 50 mm dia. 3000 mm long heavy<br />

duty GI pipe electrode<br />

7 Street lighting poles 14 SWG TC wire<br />

Note 1: Conductors above ground shall be of galvanised steel to prevent atmospheric<br />

corrosion.<br />

Note 2: Conductors buried in ground or embedded in concrete shall be of mild steel.<br />

15.21 Power capacitor.<br />

Power shunt capacitors in general shall confirm to latest version of IS:13585,<br />

Part-1. Power capacitor control panel shall be housed in metal enclosed cubicle.<br />

Power capacitor shall be mounted on MS angle frame works and capacitor control<br />

panel along with MV panel.<br />

The capacitor banks shall be complete with all parts that are necessary or essential<br />

for efficient operation. Such parts shall be deemed to be within the scope of supply<br />

whether specifically mentioned or not.<br />

The capacitor bank shall be complete with the required capacitors along with the<br />

supporting post insulators, steel rack assembly, copper bus bars, copper connecting<br />

strips, foundation channels, fuses, fuse clips, etc. The steel rack assembly shall be<br />

hot dip galvanised.<br />

GTS : General Technical Specification. Page 134