Outdoor Luminaire:<br />

The luminaire shall be 250 watt H.P.S.V. with all accessories and shall be deep<br />

drawn aluminium reflector stove enameled grey outside and brightened and<br />

annodised inside lined with felt gasket to prevent insect entry.<br />

Die cast aluminium housing covered with a lid shall be provided to accommodate<br />

all electrical accessories, such as independent ballast, power factor improvement<br />

capacitor, wired upto terminal block.<br />

A clear acrylic cover shall be fixed to the reflector by means of 4 toggles.<br />

The luminaire shall be mounted on the mast arm of 50 mm O.D. Mirror<br />

compartment and tray compartment shall have degree of protection IP 43 and IP 33<br />

respectively. The reflector shall be manufactured of drawn aluminium sheet and be<br />

painted to stove enamel grey outside and brightened and annodised inside.<br />

The housing shall be diecast aluminium - A6 Grade MBV treated covered with<br />

acrylic sheet clear.<br />

15.19 Emergency Light.<br />

Emergency light unit working on 230 volts. A.C. supply shall be self containing<br />

unit with 20 watts 600 mm long florescent lamp type ‘SWITCH ON MAIN<br />

FAILURE’. It shall be electronic automatic fluorescent type which incorporates a<br />

unit trickle charge circuit, which shall prevent overcharging of battery. The battery<br />

shall be maintenance free. The unit shall provide 4 hours illumination following<br />

power failure. The units shall generally conform to IS:9583.<br />

15.20 Earthing.<br />

Earthing in general shall comply with C.P. (Code of Practice) 3043 of Indian<br />

Standards.<br />

Earth electrode either in the form of pipe electrode or plate electrode should be<br />

provided at all premises for providing earthing system.<br />

GTS : General Technical Specification. Page 131