Exhaust Fans :<br />

Exhaust fans shall conform to the relevant Indian Standards.<br />

Exhaust fans shall be fixed at the places indicated by the Engineer-in-charge. For<br />

fixing an exhaust fan, a circular hole shall be provided in the wall to suit the size of<br />

the frame, which shall be fixed by means of rag bolts embedded to the wall. The<br />

hole shall be neatly plastered to the original finish of the wall. The exhaust fan<br />

shall be connected to exhaust fan point which shall be wired as near to the hole as<br />

possible by means of a flexible cord, care being taken that the blades rotate in the<br />

proper direction.<br />

Exhaust fans for installation in corrosive atmosphere fan shall be painted with a<br />

special PVC paint or chlorinated rubber paint (Chloro rubber paint).<br />

Installation of exhaust fans at locations need careful consideration. The regulators<br />

of ceiling fans/exhaust fans shall be connected to earth by loop earthling.<br />

Indoor Decorative Luminaires<br />

Luminaire shall be suitable for use with twin/single T.L. 40 watt 1200 mm (4’).<br />

240V fluorescent lamps, comprising of CRCA sheet steel channel stove enameled<br />

grey which incorporates all electrical accessories like quick fit lamp holder, starter<br />

holder, polyester filled ballast, power factor correction capacitor and duly prewired<br />

upto the terminal block, with earthling arrangement facility, cover made for channel<br />

from CRCA sheet steel stove white enameled covering the channel fixed by twin<br />

screw, suitable for ceiling or pendent mounting suitable for 19mm dia conduit,<br />

reflector plate for acrylic diffuser and end covers, complete in all respects ready for<br />

use. The luminaire shall conform to IS:1913.<br />

Outdoor Lighting.<br />

Poles:<br />

Street light poles shall be steel tubular swaged type, conforming to IS:2713 - 1969.,<br />

suitably long with M.S. base plate with pipe cap and over hung 2 metres long<br />

having dia. to suit the socket of 70/250 watts, 240V, High pressure sodium vapour<br />

lamp or metal halide fitting.<br />

GTS : General Technical Specification. Page 130