All outlets such as switches, wall sockets etc. shall be flush type.<br />

The outlet box shall be same as above and shall be mounted flush with the wall.<br />

The metal box shall be efficiently earthed with conduit by an approved means of<br />

earth attachment.<br />

To facilitate drawings of wire in the conduit. G.I mesh wire of 10 SWG shall be<br />

provided while laying of recessed conduit.<br />

Fans, Regulators and Clamps (IS:374):<br />

Ceiling fans including their suspension shall conform to relevant Indian Standards.<br />

All ceiling fans shall be wired to ceiling roses or to a special connector boxes and<br />

suspended from hooks or shackles with insulators between hooks and suspension<br />

rods. There shall be no joint in the suspension rod<br />

For concrete roofs, ceiling fan hooks shall be buried in the concrete during<br />

construction. M.S. flat of size 40 mm x 60 x mm bent in the form of an inverted<br />

‘U’ supported on two cross rods or cross flats. 60 mm long which are bound<br />

together to the top reinforcement of the roof shall be used. The distance between<br />

the vertical legs shall not be less than 15 cm. and the legs shall project at least<br />

13cm below the ceiling and oval holes shall be made in them for carrying a 15 cm<br />

dia. rod hook.<br />

Alternatively a 15mm dia, MS rod in the shape of ‘U’ with their vertical legs bent<br />

horizontally at the top at least 19cm. on either side and bound to the top<br />

reinforcement of the roof shall be used.<br />

In building with concrete roofs having a low ceiling height where the fan clamp<br />

mentioned under clause (c) can not be used or whatever specified, recessed type fan<br />

clamp inside a cast iron box shall be used.<br />

Canopies on top of suspension rod shall effectively hide the suspension.<br />

Unless otherwise specified all ceiling fan shall be hung 2.75m above the floor.<br />

In the case of measurement of extra down rod for ceiling fan including writing the<br />

same shall be measured in units of 10cms. Any lengths less than 5cm. shall be<br />

ignored.<br />

GTS : General Technical Specification. Page 129